4.5.8.7
Settings
Table 574:
78V Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
2.0...30.0
deg
0.1
6.0
Pickup value for vector shift
Table 575:
78V Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Over Volt Blk value
0.40...1.50
xUn
0.01
1.20
Voltage above which function will be internally
blocked
Under Volt Blk value
0.15...1.00
xUn
0.01
0.80
Voltage below which function will be internally
blocked
Table 576:
78V Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Table 577:
78V Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Phase supervision
7=Ph A + B + C
8=Pos sequence
8=Pos sequence
Monitored voltage phase
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
671
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......