Table 20. Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz/100 kHz burst disturbance
test:
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
• Common mode
2.5 kV
• Differential mode
2.5 kV
3/10/30 MHz burst disturbance test:
IEC 61000-4-18
• Common mode
2 kV
Electrostatic discharge test:
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
• Contact discharge
8 kV
• Air discharge
15 kV
Radio frequency interference tests:
10 V (rms)
f=150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-22-6, class III
10 V/m (rms)
f=80...2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f=900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f=80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance tests:
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
• All ports
4 kV
Surge immunity test:
IEC 61000-4-5
IEC 60255-22-5
• Communication
2 kV, line-to-earth
• Other ports
4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz) magnetic
field:
IEC 61000-4-8
• Continuous
• 1...3 s
300 A/m
1000 A/m
Pulse magnetic field immunity test
1000 A/m
IEC 61000-4-9
Damped oscillatory magnetic field
immunity test
100 A/m
IEC 61000-4-10
Voltage dips and short interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
> 95%/5000 ms
IEC 61000-4-11
Busbar and Multipurpose Differential Protection and Control
1MRS757467 B
REB611
Product version: 1.0
ABB
17