Table 12. Double-pole power output relays with TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC (two
contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC (2.4 VA)
Trip-circuit supervision (TCS):
• Control voltage range
20...250 V AC/DC
• Current drain through the supervision circuit
~1.5 mA
• Minimum voltage over the TCS contact
20 V AC/DC (15...20 V)
Table 13. Single-pole power output relays
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
1 A / 0.25 A / 0.15 A
Minimum contact load
100 mA at 24 V AC/DC (2.4 VA)
Table 14. Front port Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
Front
TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
Table 15. Station communication link, fibre-optic
Connector
Fibre type
1)
Wave length
Max. distance
Permitted path attenuation
2)
LC
MM 62.5/125 μm glass
fibre core
1300 nm
2 km
< 8 dB
1)
(MM) multi-mode fibre, (SM) single-mode fibre
2)
Maximum allowed attenuation caused by connectors and cable together
Busbar and Multipurpose Differential Protection and Control
1MRS757467 B
REB611
Product version: 1.0
ABB