13. Technical data
Table 3. Dimensions
Description
Value
Width
Frame
Case
177 mm
164 mm
Height
Frame
Case
177 mm (4U)
160 mm
Depth
Case
149.3 mm
Weight
Protection relay
Spare unit
3.5 kg
1.8 kg
Table 4. Power supply
Description
Value
Type
REF610CxxHxxx
REF610CxxLxxx
U
aux
rated
U
r
= 100/110/120/220/240 V AC
U
r
= 110/125/220/250 V DC
U
r
= 24/48/60 V DC
U
aux
variation (temporary)
85...110% of U
r
(AC)
80...120% of U
r
(DC)
80...120% of U
r
(DC)
Burden of auxiliary voltage supply under
quiescent (P
q
)/operating condition
<9 W/13 W
Ripple in the DC auxiliary voltage
Max. 12% of the DC value (at frequency ogf 100 Hz)
Interruption time in the auxiliary DC voltage
without resetting the protection relay
<50 ms at U
aux
rated
Time to trip from switching on the auxiliary
voltage
<350 ms
Internal over temperature limit
+100 ºC
Fuse type
T2A/250 V
Table 5. Energizing inputs
Description
Value
Rated frequency
50/60 Hz ±5 Hz
Rated current, I
n
0.2 A
1 A
5 A
Thermal withstand capability
• Continuously
0.5 A
4 A
20 A
• For 1 s
20 A
100 A
500 A
• For 10 s
5 A
25 A
100 A
Dynamic current withstand
• Half-wave value
50 A
250 A
1250 A
Input impedance
<750 mΩ
<100 mΩ
<20 mΩ
Feeder Protection
1MRS756295 G
REF610
Product version: C
ABB
9
Содержание RELION 610 Series
Страница 1: ... RELION 610 SERIES Feeder Protection REF610 Product Guide ...
Страница 27: ...27 ...