Name
Type
Description
VPS1S2TR
BOOLEAN
Status of the apparatuses between bus section 1 and 2
are valid
VP189TR
BOOLEAN
Switch status of 189 is valid (open or closed)
VP289TR
BOOLEAN
Switch status of 289 is valid (open or closed)
11.5.4.6
Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
11.5.5
Interlocking for bus-section disconnector A1A2_DC (3)
11.5.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-section
disconnector
A1A2_DC
-
3
11.5.5.2
Functionality
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one bus-
section disconnector between section 1 and 2 according to figure
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)
WA2 (A2)
189G
289G
A1A2_DC
en04000492_ansi.vsd
52
ANSI04000492 V1 EN
Figure 201:
Switchyard layout A1A2_DC (3)
1MRK 506 335-UUS A
Section 11
Control
417
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...