200°
Reverse
Forward
20°
en06000385.vsd
IEC06000385 V1 EN
Figure 69:
Directional element used to release the measured angle between V
o
and
I
0
The input radians are summarized with an offset angle and the result evaluated. If the angle
is within the boundaries for a specific sector, the phase indication for that sector will be
active see figure
. Only one sector signal is allowed to be activated at the same time.
The sector function for condition 1 has an internal release signal which is active if the main
sequence function has classified the angle between V
0
and I
0
as valid. The following
conditions must be fulfilled for activating the release signals:
|V
2
|>
V2MinOp
|3I
0
|> 0.05 ·
IBase
|3I
0
|>maxIph ·
INRelPG
where:
V
2
and 3I
0
are the magnitude of the negative sequence voltage and zero-
sequence current (3I
0
)
V2MinOp
is the setting parameter for minimum operating negative sequence
voltage
maxIph
is the maximum phase current
The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.
The condition 2 looks at the angle relationship between the negative sequence voltage V
2
and the positive sequence voltage V
1
. Since this is a phase-to-phase voltage relationship,
there is no need for shifting phases if the fault is in reverse direction. A phase shift is
1MRK 506 335-UUS A
Section 6
Impedance protection
155
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...