107
Supervision of AC input quantities (DA)
Chapter 8
Monitoring
Table 119: Setting parameters for the AC monitoring (DAnn-) function block
Parameter
Range
Default
Unit
Description
For each voltage input channels U1 - U5:
DA01--DA05
Operation
Off, On
Off
-
Operating mode for DAnn function
Hysteres
0.0-1999.9
Step: 0.1
5.0
kV
Alarm hysteres for U1 - U5
EnAlRem
Off, On
On
-
Immediate event when an alarm is disabled
for U1 - U5 (produces an immediate event at
reset of any alarm monitoring element, when
On)
EnAlarms
Off, On
On
-
Set to 'On' to activate alarm supervision for
U1 - U5 (produces an immediate event at
operation of any alarm monitoring element,
when On)
HiAlarm
0.0-1999.9
Step: 0.1
220.0
kV
High Alarm level for U1 - U5
HiWarn
0.0-1999.9
Step: 0.1
210.0
kV
High Warning level for U1 - U5
LowWarn
0.0-1999.9
Step: 0.1
170.0
kV
Low Warning level for U1 - U5
LowAlarm
0.0-1999.9
Step. 0.1
160.0
kV
Low Alarm level for U1 - U5
RepInt
0-3600
Step: 1
0
s
Time between reports for U1 - U5 in sec-
onds. Zero = Off (duration of time interval
between two reports at periodic reporting
function. Setting to 0 disables the periodic
reporting)
EnDeadB
Off, On
Off
-
Enable amplitude dead band supervision for
U1 - U5
DeadBand
0.0-1999.9
Step: 0.1
5.0
kV
Amplitude dead band for U1 - U5
EnIDeadB
Off, On
Off
-
Enable integrating dead band supervision for
U1 - U5
IDeadB
0.0-1999.9
Step: 0.1
10.0
kV
Integrating dead band for U1 - U5
EnDeadBP
Off, On
Off
-
Enable periodic dead band reporting U1 - U5
For each current input channels I1 - I5:
DA06 - DA10
Operation
Off, On
Off
-
Operating mode for DAnn function
Hysteres
0-99999
Step: 1
50
A
Alarm hysteresis for I1 - I5
EnAlRem
Off, On
On
-
Immediate event when an alarm is disabled
for I1 - I5 (produces an immediate event at
reset of any alarm monitoring element, when
On)
Содержание REL 551-C1*2.5
Страница 1: ...Technical reference manual ProtectIT Line differential protection terminal REL 551 C1 2 5 ...
Страница 23: ...14 Introduction to the technical reference manual Chapter 1 Introduction ...
Страница 39: ...30 Technical data Chapter 2 General ...
Страница 63: ...54 Blocking of signals during test BST Chapter 3 Common functions ...
Страница 71: ...62 Line differential protection phase segregated DIFL Chapter 4 Line differential protection ...
Страница 89: ...80 Thermal phase overload protection THOL Chapter 5 Current ...
Страница 101: ...92 Event function EV Chapter 7 Logic ...
Страница 160: ...151 Chapter 11 Diagrams Chapter 11 Diagrams This chapter contains the terminal diagrams for the terminal ...
Страница 162: ...153 Terminal diagrams Chapter 11 Diagrams 1 2 Terminal diagram REL 551 C1 Figure 38 REL 551 C1 ...
Страница 163: ...154 Terminal diagrams Chapter 11 Diagrams Figure 39 REL 551 C1 with DC switch ...
Страница 167: ...158 Terminal diagrams Chapter 11 Diagrams ...