27
Configuration
&KDSWHU
8QGHUV0,WUHH
Slave number and baud rate (communication speed) must be set for both the ports.
These settings must correspond with the settings in the used PC-program. For the rear
port it is possible to set permission of changes between active setting groups, ActGr-
pRestrict, and the setting restrictions, SettingRestrict, as well.
,(&FRPPXQLFDWLRQ
Use this menu to set slave number and baud rate when to communicate on the IEC 870–
5–103 communications bus, also known as
6FKQLWWVWHOOH
or VDEW 6. The IEC bus
uses the same rear optic port as the SPA bus, but the settings must be done separately.
/21FRPPXQLFDWLRQ
Use this menu to view node information as address and location, (set from the LON
Network Tool), as well as the Neuron identity. Functions for address setting during in-
stallation (ServicePinMSG), LON configuration reset (LONDefault) and session timers
are also available.
5HPRWHWHUPLQDOFRPPXQLFDWLRQ
Use this menu to configure the 56/64 kbit data communication to remote terminal. This
communication requires a certain data communication module. The parameters to set
are:
•
the local terminal identity
•
the remote terminal identity
•
the bit rate
•
the fiber optics transmitter output power (not applicable for galvanic interface)
•
the terminal master/slave operation.
7LPH
The internal terminal time can be synchronised with an external unit connected to the
SPA/IEC 60870-5-103 port or the LON port. It is also possible to use a minute pulse
synchronisation signal connected to a digital input.
'LVWXUE5HSRUW
This menu includes all setting parameters for the disturbance report. The following fea-
ture is available:
1RWH
6HVVLRQWLPHUVDUHIRUDGYDQFHGXVDJHDQGVKRXOGRQO\EHFKDQJHGXSRQUHFRPPHQGD
WLRQIURP$%%