70
1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
9.
Check lists
Table 9.-1 Setting group 1
Variable
Group 1
(R, W, P)
Setting range
Default
setting
Customer’s
setting
Set start value of stage I
0
>
S41
1.0...100% x I
n
1.0% x I
n
Set start value of stage U
0
>
S42
2.0...80.0% x U
n
2.0% x U
n
Operate time of stage I
0
>/U
0
>
S43
0.10...300 s
0.10 s
Time multiplier k of stage I
0
>
S44
0.05...1.00
0.05
Set start value of stage I
0
>>
S45
5.0...400% x I
n
5.0% x I
n
Set start value of stage U
0
>>
S46
2.0...80.0% x U
n
2.0% x U
n
Operate time of stage I
0
>>/
U
0
>>
S47
0.10...300 s
0.10 s
Set start value of stage U
0b
>
S48
2.0...80.0% x U
n
2.0% x U
n
Operate time of stage U
0b
>
S49
0.10...300 s
0.10 s
Additional angle (
ϕ
a
) of stage
I
0
>/I
0
>> with the basic angle
S50
0...90
°
0
°
Basic angle (
ϕ
b
) of stage I
0
>/
I
0
>>
S51
-90...0
°
-90
°
Angle correction (
ϕ
c
) of stage
I
0
>/ I
0
>> with the I
ϕ
characteristic
S52
2...7
°
2
°
Checksum, SGF1
S53
0...31
0
Checksum, SGF2
S54
0...255
0
Checksum, SGF3
S55
0...255
0
Checksum, SGF4
S56
0...32
0
Checksum, SGF5
S57
0...4
0
Checksum, SGB1
S58
0...255
0
Checksum, SGR1
S59
0...15
12
Checksum, SGR2
S60
0...15
3
Checksum, SGR3
S61
0...15
12
Checksum, SGR4
S62
0...15
3
Checksum, SGR5
S63
0...15
12
Checksum, SGR6
S64
0...15
3