3.  Available functions

Main protection functions

IEC 61850 or
Function name

ANSI

Function description

Generator

 

 

 

 

REG650

REG650 (B01)

Gen diff

REG650 (B05)

Gen+Trafo diff

 

Differential protection

 

 

T3WPDIF

87T

Transformer differential protection, three winding

0–1

 

1

 

REFPDIF

87N

Restricted earth fault protection, low impedance

0–1

 

 

 

HZPDIF

87

1Ph High impedance differential protection

0–1

1

1

 

GENPDIF

87G

Generator differential protection

0–1

1

 

 

Impedance protection

 

 

ZMRPSB

68

Power swing detection

0–1

 

 

 

ZGCPDIS

21G

Underimpedance protection for generators and transformers

0–1

1

1

 

LEXPDIS

40

Loss of excitation

0–1

1

1

 

OOSPPAM

78

Out-of-step protection

0–1

1

1

 

LEPDIS

 

Load encroachment

0–1

1

1

 

Generator protection REG650

1MRK 502 050-BEN B

 

Product version: 1.3

 
 

6

ABB

Содержание REG650 ANSI

Страница 1: ...Relion 650 series Generator protection REG650 Product guide...

Страница 2: ...Ordering for Customized IED 63 21 Ordering for Configured IED 67 22 Ordering for Accessories 69 Disclaimer The information in this document is subject to change without notice and should not be constr...

Страница 3: ...s 2 Application REG650 is used for the protection and monitoring of generating plants The IED is especially suitable for applications in distributed control systems with high demands on reliability It...

Страница 4: ...PDIF 87N IdN 2 Input for independent non directional EF function It can be used for different purposes e g as stator EF protection or turn to turn protection for generators with split winding or even...

Страница 5: ...87N IdN EF4 PTOC 51N IN GT01 ROV2 PTOV 59N 3Uo 59N UN Y Y CV MMXN Meter GOP PDOP 32 P TRM module with 4I 1I 5U AIM module with 6I 4U Requires dedicated CT cores external resistor and metrosil for cor...

Страница 6: ...d earth fault protection low impedance 0 1 HZPDIF 87 1Ph High impedance differential protection 0 1 1 1 GENPDIF 87G Generator differential protection 0 1 1 Impedance protection ZMRPSB 68 Power swing d...

Страница 7: ...nderpower protection 0 1 1 1 GOPPDOP 32 Directional overpower protection 0 2 2 2 AEGGAPC 50AE Accidental energizing protection for synchronous generator 1 1 1 NS2PTOC 46I2 Negative sequence time overc...

Страница 8: ...d select for IEC60870 5 103 50 50 50 Apparatus control and Interlocking APC8 Apparatus control for single bay max 8 app 1CB incl interlocking 0 1 QCBAY Bay control 1 1 1 LOCREM Handling of LR switch p...

Страница 9: ...version with logic node representation 16 16 16 IB16A Integer to Boolean 16 conversion 16 16 16 IB16FCVB Integer to Boolean 16 conversion with logic node representation 16 16 16 TEIGGIO Elapsed time i...

Страница 10: ...ulation gas monitoring function 0 2 2 2 SSIML 71 Insulation liquid monitoring function 0 2 2 2 SSCBR Circuit breaker condition monitoring 0 1 1 1 I103MEAS Measurands for IEC60870 5 103 1 1 1 I103MEASU...

Страница 11: ...r TCP IP communication protocol 1 1 1 RS485GEN RS485 1 1 1 OPTICALPROT Operation selection for optical serial 1 1 1 RS485PROT Operation selection for RS485 1 1 1 DNPFREC DNP3 0 fault records for TCP I...

Страница 12: ...Time synchronization 1 DTSBEGIN DTSEND TIMEZONE Time synchronization daylight saving 1 IRIG B Time synchronization 1 SETGRPS Setting group handling 1 ACTVGRP Parameter setting groups 1 TESTMODE Test...

Страница 13: ...differential protection HZPDIF The 1Ph High impedance differential protection HZPDIF functions can be used when the involved CT cores have the same turns ratio and similar magnetizing characteristics...

Страница 14: ...tion area No operation area No operation area IEC07000117 V2 EN Figure 4 Load encroachment influence on the offset mho Z3 characteristic Loss of excitation LEXPDIS There are limits for the low excitat...

Страница 15: ...agnitude of the fault current is almost independent on the fault location in the network The protection can be selected to use either the residual current 3I0 cosj or 3I0 j or residual power component...

Страница 16: ...of generators against possible overheating of the rotor caused by negative sequence current in the stator current The negative sequence currents in a generator may among others be caused by Unbalanced...

Страница 17: ...to flow These eddy currents can cause excessive heating and severe damage to insulation and adjacent parts in a relatively short time The function has settable inverse operating curves and independent...

Страница 18: ...of high fundamental power system frequency is needed Overfrequency occurs because of sudden load drops or shunt faults in the power network Close to the generating plant generator governor problems c...

Страница 19: ...ion checks that the voltages on both sides of the circuit breaker are in synchronism or with at least one side dead to ensure that closing can be done safely SESRSYN function includes a built in volta...

Страница 20: ...nals from the local HMI or from an external local remote switch are applied via the function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function block A parameter in function block LOCREM i...

Страница 21: ...ecific application needs for settable pulse or steady output Configurable logic blocks A number of logic blocks and timers are available for the user to adapt the configuration to the specific applica...

Страница 22: ...an be used in the configuration of an IED either for forcing the unused inputs in other function blocks to a certain level value or for creating certain logic Boolean integer floating point string typ...

Страница 23: ...ent list DRPRDRE Continuous event logging is useful for monitoring the system from an overview perspective and is a complement to specific disturbance recorder functions The event list logs all binary...

Страница 24: ...ltage and undervoltage alarms can be set according to definite time characteristics SPVNZBAT operates after a settable operate time and resets when the battery undervoltage or overvoltage condition di...

Страница 25: ...e tagging of internal events and disturbances are an excellent help when evaluating faults Without time synchronization only the events within the IED can be compared to one another With time synchron...

Страница 26: ...otiate with explicit SSL via AUTH SSL TLS Using FTP without SSL encryption gives the FTP client reduced capabilities This mode is only for accessing disturbance recorder data from the IED If normal FT...

Страница 27: ...are placed on integrated communication modules The IED is connected to Ethernet based communication systems via the fibre optic multimode LC connector s 100BASE FX The IED supports SNTP and IRIG B tim...

Страница 28: ...e selection is made at ordering Redundant station bus communication according to IEC 62439 3 Edition 2 uses both ports LAN1A and LAN1B on the COM03 module Select COM03 for redundant station bus accord...

Страница 29: ...ams can be downloaded from http www abb com substationautomation Connection diagrams for Customized products Connection diagram 650 series 1 3 1MRK006501 AD Connection diagrams for Configured products...

Страница 30: ...this document are only valid under the following circumstances CT and VT ratios in the IED are set in accordance with the associated main instrument transformers Note that for functions which measure...

Страница 31: ...amic withstand 250 A one half wave 1250 A one half wave Burden 1 mVA at Ir 0 1 A 10 mVA at Ir 1 A 20 mVA at Ir 0 5 A 200 mVA at Ir 5 A max 350 A for 1 s when COMBITEST test switch is included Voltage...

Страница 32: ...t in PSM module 1 bit represents 0 5 V 1 VDC 1 bit represents 1 V 1 VDC 1 bit represents 2 V 1 VDC Binary inputs and outputs Table 4 Binary inputs Description Value Operating range Maximum input volta...

Страница 33: ...ver the TCS contact 20 V DC Table 8 Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate 100BASE TX CAT 6 S FTP or better 100 MBits s 100BASE FX TCP IP protocol Fibre optic cable w...

Страница 34: ...ided Table 13 Serial rear interface Type Counter connector Serial port X9 Optical serial port type ST for IEC 60870 5 103 and DNP serial Table 14 Optical serial port X9 Wave length Fibre type Connecto...

Страница 35: ...ansport and storage temperature range 40 85 C Table 17 Environmental tests Description Type test value Reference Cold tests operation storage 96 h at 25 C 16 h at 40 C 96 h at 40 C IEC 60068 2 1 ANSI...

Страница 36: ...4 4 IEC 60255 22 4 class A ANSI C37 90 1 2012 Communication ports 4 kV Other ports 4 kV Surge immunity test IEC 61000 4 5 IEC 60255 22 5 Communication 1 kV line to earth Other ports 2 kV line to eart...

Страница 37: ...IEC 30 230 MHz 40 dB V m quasi peak measured at 10 m distance 230 1000 MHz 47 dB V m quasi peak measured at 10 m distance Table 19 Insulation tests Description Type test value Reference Dielectric te...

Страница 38: ...thstand test IEC 60255 21 2 Class 1 Bump test IEC 60255 21 2 Class 1 Seismic test IEC 60255 21 3 Class 2 Product safety Table 21 Product safety Description Reference LV directive 2006 95 EC Standard E...

Страница 39: ...pically at 0 to 5 x set level Reset time restrained function 25 ms typically at 5 to 0 x set level Operate time unrestrained function 20 ms typically at 0 to 5 x set level Reset time unrestrained func...

Страница 40: ...1 0 of set value Reset ratio 90 Base sensitivity function 0 10 1 00 p u of IBase 1 0 of Ir Negative sequence current level 0 02 0 4 p u of IBase 1 0 of Ir Operate time restrained function 40 ms typic...

Страница 41: ...gle at 85 degrees Reverse positive sequence impedance 0 005 3000 000 phase Angle for positive sequence impedance 10 90 degrees Timers 0 000 60 000 s 0 5 10 ms Operate time 25 ms typically Reset ratio...

Страница 42: ...locking 5 100 of fundamental 2 0 of Ir Independent time delay 0 000 60 000 s 0 5 25 ms Minimum operate time for inverse characteristics 0 000 60 000 s 0 5 25 ms Inverse characteristics see table 74 ta...

Страница 43: ...t Minimum polarizing voltage Zero sequence 1 100 of UBase 0 5 of Ur Minimum polarizing voltage Negative sequence 1 100 of UBase 0 5 of Ur Minimum polarizing current Zero sequence 2 100 of IBase 1 0 of...

Страница 44: ...n directional residual overvoltage 1 00 200 00 of UBase 0 5 of Ur at U Ur 0 5 of U at U Ur Residual release current for all directional modes 0 25 200 00 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir At...

Страница 45: ...r current 35 ms typically at 0 to 2 x Iset Impulse margin time non directional residual over current 25 ms typically Table 35 Thermal overload protection two time constants TRPTTR Function Range or va...

Страница 46: ...perate time for current detection 20 ms typically Reset time for current detection 10 ms maximum Table 37 Pole discordance protection CCRPLD Function Range or value Accuracy Operate value current asym...

Страница 47: ...f U at U Ur Timers 0 000 60 000 s 0 5 25 ms Table 40 Negative sequence time overcurrent protection for machines NS2PTOC Function Range or value Accuracy Operate value step 1 and 2 negative sequence ov...

Страница 48: ...pendent operation 30 100 of UBase 1 0 of Ur Reset ratio overcurrent 95 Reset ratio undervoltage 105 Overcurrent Critical impulse time Impulse margin time 10 ms typically at 0 to 2 x Iset 15 ms typical...

Страница 49: ...15 ms typically Table 44 Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage step 1 1 200 of UBase 0 5 of Ur at U Ur 0 5 of U at U Ur Operate voltage ste...

Страница 50: ...verse function 0 000 60 000 s 0 5 25 ms Alarm time delay 0 00 9000 00 0 5 25 ms Table 46 100 Stator E F 3rd harmonic STEFPHIZ Function Range or value Accuracy Fundamental frequency level UN 95 Stator...

Страница 51: ...48 Overfrequency protection SAPTOF Function Range or value Accuracy Operate value start function 35 00 75 00 Hz 2 0 mHz at symmetrical three phase voltage Reset ratio 0 999 Operate time start function...

Страница 52: ...Ir Operate voltage change level 1 100 of UBase 5 0 of Ur Operate current change level 1 100 of IBase 5 0 of Ir Operate phase voltage 1 100 of UBase 0 5 of Ur Operate phase current 1 100 of IBase 1 0...

Страница 53: ...mHz Frequency difference maximum limit for synchronizing 0 050 0 500 Hz 2 0 mHz Maximum allowed frequency rate of change 0 000 0 500 Hz s 10 0 mHz s Closing time of the breaker 0 000 60 000 s 0 5 25...

Страница 54: ...ime Range or value Accuracy 20 ms 100 ms ANDQT 20 100 ORQT 20 100 XORQT 10 30 INVERTERQT 20 100 RSMEMORYQT 10 30 SRMEMORYQT 15 10 PULSETIMERQT 10 30 0 000 90000 000 s 0 5 25 ms for 20 ms cycle time TI...

Страница 55: ...r 1 0 of Sr at S Sr 1 0 of S at S Sr Apparent power S 0 1 x Ur U 1 5 x Ur 0 2 x Ir I 4 0 x Ir 1 0 of Sr at S Sr 1 0 of S at S Sr Apparent power S Three phase settings cos phi 1 0 5 of S at S Sr 0 5 of...

Страница 56: ...e report 96 Maximum number of events in the Event recording per recording 150 Maximum number of events in the Event list 1000 first in first out Maximum total recording time 3 4 s recording time and m...

Страница 57: ...maximum number of channels typical value 340 seconds 100 recordings at 50 Hz 280 seconds 80 recordings at 60 Hz Table 66 Station battery supervision SPVNZBAT Function Range or value Accuracy Lower li...

Страница 58: ...e alarm 0 00 60 00 s 0 5 25 ms Time delay for gas pressure lockout 0 00 60 00 s 0 5 25 ms Metering Table 70 Pulse counter PCGGIO Function Setting range Accuracy Cycle time for report of counter value...

Страница 59: ...or the IEDs 100BASE FX Protocol serial IEC 60870 5 103 Communication speed for the IEDs 9600 or 19200 Bd Protocol serial DNP3 0 Communication speed for the IEDs 300 115200 Bd Hardware IED Dimensions T...

Страница 60: ...e Very Inverse A 28 55 B 0 712 P 2 0 ANSI Long Time Inverse A 0 086 B 0 185 P 0 02 Table 75 IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic 1 P A t k I EQUAT...

Страница 61: ...Iset k 0 05 999 in steps of 0 01 Table 77 Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve t k U U U EQUATION1436 SMALL V1 EN U Uset U Umeasured k...

Страница 62: ...10 in steps of 0 01 Table 79 Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve t k U U U EQUATION1436 SMALL V1 EN U Uset U Umeasured k 0 05...

Страница 63: ...erminals 1MRK 002 960 EA Ring lug terminals 1MRK 002 960 FA Power supply module Rule One Power supply module must be specified Power supply module PSM01 24 30V DC 9BO 1KHL178029R0001 PSM02 48 125V DC...

Страница 64: ...output OC4PTOC Qty 1 2 1MRK 004 908 BC Four step residual overcurrent protection zero negative sequence direction EF4PTOC Qty 1 2 1MRK 004 908 FA Sensitive directional residual overcurrent and power...

Страница 65: ...GA Circuit breaker for 1 CB CBC1 Qty 1MRK 004 918 AA Circuit breaker for 2 CB CBC2 Qty 1MRK 004 918 BA Logic Configurable logic blocks Q T 1MRK 002 917 MK Monitoring Station battery supervision SPVNZB...

Страница 66: ...20V 50 60Hz Qty 1KHL178083R0016 Transformer module TRM01 4I 1 5A 6U 100 220V 50 60Hz Qty 1KHL178083R0003 Rule Only one Analog input module can be ordered Analog input module AIM01 6I 1 5A 4U 100 220V...

Страница 67: ...rsion no 1 3 Selection for position 1 1 3 Configuration alternatives 2 Notes and Rules Generator protection B01 Generator Transformer protection B05 ACT configuration ABB standard configuration X00 Se...

Страница 68: ...inals S Ringlug terminals R Analog system Slot position p2 Transformer module TRM01 4I 1 5A 1I 0 1 0 5A 5U 100 220V 50 60Hz A3 Slot position p4 Analog input module AIM01 6I 1 5A 4U 100 220V 50 60Hz B1...

Страница 69: ...rth fault protection RXTTE 4 Quantity 1MRK 002 108 BA Protective resistor on plate R1 100 R2 120 Quantity RK 795 102 AD Protective resistor on plate R1 560 R2 560 Quantity RK 795 102 AB Manuals Note O...

Страница 70: ...tity 1MRK 511 281 UEN Communication protocol manual IEC 60870 5 103 IEC Quantity 1MRK 511 282 UEN Engineering manual IEC Quantity 1MRK 511 284 UEN Installation manual IEC Quantity 1MRK 514 016 UEN Poi...

Страница 71: ...ries manuals Identity number Communication protocol manual DNP 3 0 1MRK 511 280 UEN Communication protocol manual IEC 61850 8 1 1MRK 511 281 UEN Communication protocol manual IEC 60870 5 103 1MRK 511...