LED 3
UNBALANCE PROTECTION
NSPTOC1
I
2
>(1)
46(1)
BLOCK
START
OPERATE
3I
ENA_MULT
NSPTOC2
I
2
>(2)
46(2)
BLOCK
START
OPERATE
3I
ENA_MULT
OSWGAPC10
OR
OUT
IN_13
IN_14
IN_15
SELGAPC4
IN_12
OUT_3
PDNSPTOC1
I
2
/I
1
(1)
46PD(1)
BLOCK
START
OPERATE
3I
GUID-33B6922D-228D-4D26-98AF-6043981814C0 V1 EN
Figure 109:
Unbalance protection
Two negative-sequence overcurrent stages NSPTOC1 and NSPTOC2 and one phase
discontinuity stage PDNPSTOC1 are offered for unbalance protection. The phase
discontinuity protection PDNPSTOC1 provides protection for interruptions in the
normal three-phase load supply, for example, in downed conductor situations.
The operate signals of these unbalance protections are connected to the Master Trip
and to alarm LED 3.
Section 3
1MRS757456 D
REF611 standardized configurations
128
REF611
Application Manual