If you do not cancel the test mode, it remains on and the Ready LED
remains blinking. Test mode does not retain if the IED is reset.
6.4.3
Connecting to trip and disturbance recorder functions
PCM600 can be used for connecting trip and disturbance recorder functions.
For more information, see PCM600 documentation.
6.4.4
Defining disturbance recorder channel settings
1.
Select
Main Menu/Configuration/Disturbance recorder/Channel settings
.
2.
Press
or
to scroll the view.
3.
To change channel settings, press
.
Each analog channel has an equal set of parameters and correspondingly, each binary
channel has an equal set of parameters.
6.4.5
Defining setting group
6.4.5.1
Activating a setting group
IED settings are planned in advance for different operation conditions by calculating
setting values to different setting groups. The active setting group can be changed by
the IED application or manually from the menu.
1.
Select
Main Menu/Settings/Setting group/Active group
and press
.
A071150 V3 EN
Figure 53:
Active setting group
2.
Select the setting group with
or
.
3.
Press
to confirm the selection or
to cancel.
1MRS756499 A
Section 6
Operating procedures
RED615
73
Operation Manual