CCBRBRF1_TRBU
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
DARREC1_CLOSE_CB
X110_BI3_GAS_PRESSURE_ALARM
X110_BI4_CB_SPRING_CHARGED
PHIPTOC1_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
NSPTOC1_OPERATE
PHHPTOC2_OPERATE
NSPTOC2_OPERATE
EFIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
T1PTTR1_OPERATE
PDNSPTOC1_OPERATE
T2PTTR1_OPERATE
LNPLDF1_OPERATE
CCBRBRF1_TRRET
X120_BI1_EXT_OC_BLOCKING
INRPHAR1_BLK2H
LNPLDF1_PROT_NOT_ACTIVE
PCSITPC1_ALARM
PHIPTOC1_START
PHHPTOC1_START
PHHPTOC2_START
PHLPTOC1_START
T1PTTR1_START
DARREC1_UNSUC_RECL
DARREC1_INPRO
CCSPVC1_ALARM
T2PTTR1_ALARM
T1PTTR1_ALARM
T2PTTR1_START
PDNSPTOC1_START
NSPTOC1_START
NSPTOC2_START
EFHPTOC1_START
EFIPTOC1_START
EFLPTOC1_START
EFLPTOC2_START
LNPLDF_BLKD2H
LNPLDF1_START
DISTURB_RECORD_TRIGGERED
GUID-C658211A-FDF1-4ECB-AD66-34E603CE8E4A V2 EN
Figure 27:
Disturbance recorder
3.3.3.3
Functional diagrams for condition monitoring
CCSPVC1 detects failures in the current measuring circuits. When a failure is
detected, it can be used to block the current protection functions that measure
calculated sequence component currents or residual current to avoid unnecessary
operation.
CCSPVC1
BLOCK
FAIL
ALARM
CCSPVC1_FAIL
CCSPVC1_ALARM
GUID-57D1F65C-2438-4C84-926D-8D21A1FAB8E7 V2 EN
Figure 28:
Current circuit supervision function
Circuit-breaker condition monitoring SSCBR1 supervises the switch status based on
the connected binary input information and the measured current levels. SSCBR1
introduces various supervision methods.
Section 3
1MRS758127 C
RED615 standard configurations
50
RED615
Application Manual