Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Quantity
Rated value
Nominal range
Current
I
r
= 1 or 5 A
(0-1.8) × I
r
at I
r
= 1 A
(0-1.6) × I
r
at I
r
= 5 A
Permissive overload
1.1 × I
r
cont.
1.8 × I
r
for 30 min at I
r
= 1 A
1.6 × I
r
for 30 min at I
r
= 5 A
Burden
< 350 mVA at I
r
= 5 A
< 200 mVA at I
r
= 1 A
Ac voltage
U
r
= 110 V
0.5–288 V
Operative range
(0–340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
< 20 mVA at 110 V
Frequency
f
r
= 50/60 Hz
±5%
M6389-1 v4
Table 9. MIM - mA input module
Quantity:
Rated value:
Nominal range:
Input resistance
R
in
= 194 Ohm
-
Input range
±5, ±10, ±20mA
0-5, 0-10, 0-20, 4-20mA
-
Power consumption
each mA-board
each mA input
£
2 W
£
0.1 W
-
SEMOD55310-2 v8
Table 10. OEM - Optical ethernet module
Quantity
Rated value
Number of channels
1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118 and port C, D for IEC 61850-9-2LE / IEEE
C37.118)
Standard
IEEE 802.3u 100BASE-FX
Type of fiber
62.5/125
m
m multimode fibre
Wave length
1300 nm
Optical connector
Type ST
Communication speed
Fast Ethernet 100 Mbit/s
Auxiliary DC voltage
IP15843-1 v3
M12286-1 v4
Table 11. PSM - Power supply module
Quantity
Rated value
Nominal range
Auxiliary dc voltage, EL (input)
EL = (24 - 60) V
EL = (90 - 250) V
EL
±
20%
EL
±
20%
Power consumption
50 W typically
-
Auxiliary DC power in-rush
< 10 A during 0.1 s
-
1MRK 511 361-BEN B
Bay control REC670 2.1 IEC
Product version: 2.1
ABB
37