1MRS750500-MUM
Feeder, Machine and Transformer Terminals
Operator’s Manual
RE_ 54_
21
5.3.
User level
At user level, data is received in four different views that are displayed in the main
window:
1. MIMIC view
2. MEASUREMENT view
3. EVENT view
4. ALARM view
The assisting window gives general information on how to scroll the display. Use
the arrow buttons at user level as follows:
• Press [
→
] or [
←
] to move between the views in the main window
• Press [
↑
] or [
↓
] to scroll the event and measurement lists when there are more
items than fit to the display at a time
Manipulation of the arrow buttons does not affect indications, control of objects or
panel status.
5.3.1.
MIMIC view
When the MIMIC view is opened in the main window, the configuration picture of
the control unit is shown on the display. The MIMIC view gives the real-time status
of objects (disconnectors, circuit breakers, etc.) according to the status of the
predetermined digital inputs. The MIMIC view is the default view of the terminal
(at power up, after time-out, etc.).
mimicvie_b
Fig. 5.3.1.-1
MIMIC view
21 kV
CB OK
AROFF
[C] button functions in the MIMIC view
• Press [C] for 2 s to reset indications
• Press [C] to cancel password inquiry