![ABB RDIO-01 Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/abb/rdio-01/rdio-01_user-manual_2766024.webp)
Appendix A – Technical data
A-2
RDIO-01 User’s manual
Digital inputs:
• Input voltages: 24…250 V DC, 110…230 V AC
• Logic levels (DC): "0" < 8 V, "1" > 12 V
• Input currents: 4 mA (min), 10 mA (typical) at
24 V DC, 4 mA (typical) at 230 V AC
• Filtering time (selectable for all channels):
ON: 5…10 ms , OFF: 2 ms
• Updating interval in the ACS 800 Standard
Application Program: 12 ms (min.)
• Isolated from each other, the relay outputs, power
supply and earth. Test voltages: 2.5 kV rms, 1 minute
(DI1 and DI2+DI3); 1.5 kV rms, 1 minute (DI2 and
DI3
Relay outputs:
• Max. contact voltage: 120 V DC, 250 V AC
• Max. contact current / power: 5 A, 24 V DC; 0.4 A,
120 V DC; 1250 VA, 250 V AC
• Max. continuous current: 2 A rms
• Minimum current: 5 mA, 24 V DC
• Contact material: Silver cadmium oxide (AgCdO)
• Contact protection: Varistor (250 V)
• Isolated from each other, the digital inputs, power
supply and earth. Test voltage: 2.5 kV rms, 1 minute
General
• Max. power consumption:
150 mA (5 V) + 30 mA (24 V)
Both voltages supplied by the RMIO board
• Estimated min. lifetime: 100 000 h
• All materials UL/CSA-approved
• Complies with EMC standards EN 50081-2 and
EN 50082-2
Содержание RDIO-01
Страница 1: ...ABB Drives Digital I O Extension Module RDIO 01 User s Manual ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety Instructions iv RDIO 01 User s manual ...
Страница 14: ...Chapter 2 Overview 2 4 RDIO 01 User s manual ...
Страница 22: ...Chapter 4 Fault tracing 4 2 RDIO 01 User s manual ...
Страница 25: ......