Chapter 3 – Installation
3-4
RDIO-01 User’s manual
Terminal
designations
Marking
Description
X11
DC signal:
24 to 250 V, 4…10 mA
Signal levels: “1” > 12 V; “0” < 8 V
AC signal:
110 to 230 V ±10%, max. 4 mA
Signal levels: “1” > 40 V; “0” < 20 V
DI1:
Galvanically isolated from other digital inputs, relay
outputs and power supply (2.5 kV AC, 1 min)
DI2 and DI3:
Galvanically isolated as a group from DI1, relay
outputs and power supply (2.5 kV AC, 1 min).
Galvanically isolated from each other
(1.5 kV AC, 1 min)
1
DI1A
Dig
ital
inpu
t DI1
2
DI1B
X12
1
DI2A
Digita
l
input
DI2
2
DI2B
3
DI3A
Digital
input DI
3
4
DI3B
Marking
Description
X21
Relay outputs RO1 and RO2:
Max. continuous current: 2 A rms
Switching capability:
8 A (24 V DC, resistive load)
0.4 A (120 V DC, resistive load)
2000 VA (250 V AC)
Galvanically isolated from each
other, digital inputs and power
supply (2.5 kV AC, 1 min)
1
R1NC
Rela
y
outp
u
t 1
2
R1CM
3
R1NO
X22
1
R2NC
Re
la
y
o
u
tput 2
2
R2CM
3
R2NO
Содержание RDIO-01
Страница 1: ...ABB Drives Digital I O Extension Module RDIO 01 User s Manual ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety Instructions iv RDIO 01 User s manual ...
Страница 14: ...Chapter 2 Overview 2 4 RDIO 01 User s manual ...
Страница 22: ...Chapter 4 Fault tracing 4 2 RDIO 01 User s manual ...
Страница 25: ......