7 - Operation
10. Alarm
This section of the menu allows you to set the activation status of a relay
(available either as contact normally open – N.O. – or as contact normally
closed – N.C.).
This contact can be used, for example, to: activate a siren or a visual
alarm, control the disconnect device of an external transformer, or control
an external device.
The relay can be set to switch in 4 different modes:
• Production (display text “PRODUCTION”)
T
he relay is activated (state: switched) whenever the inverter connects
to the grid; as soon as the inverter is disconnected from the network (for
whatever reason that caused disconnection), the relay is in its resting
position
• Alarm with reset at the end of the alarm signalling process (display
text “ALARM”):
The relay is activated (state: switched) whenever an error is present
(code Exxx) on the inverter; this does not apply to warnings (Warning
– code Wxxx). The alarm returns to its resting position when the alarm
signal ends, i.e. before the inverter checks the grid parameters after the
alarm state. This is because grid control state is not an alarm state but a
state of normal operation.
Alarms for which the relay is activated
E001
E002
E003
E004
E005
E006
E007
E010
E011
E012
E013
E014
E015
E016
E017
E018
E019
E020
E021
E022
E023
E026
E029
E030
E031
E032
E033
E034
E046
E049
E050
E051
E053
E054
E055
E056
E057
E058
W003
INVERTER RUN
ERROR OCCURENCY
ERROR MESSAGE
t=15s
GRID RECONNECTION
t=based on Country Standard
ERROR
STILL
PRESENT
Yes
No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State:
Idle
Relay State: Switched
INVERTER RUN
- PRODUCTION -
GRID DISCONNECTION
- NO PRODUCTION -
GRID RECONNECTION
t=based on Country Standard
DISCONNECTION
CAUSE IS STILL
PRESENT
Yes
No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State:
Idle
Relay State: Switched