FEP630, FEH630
ELECTROMAGNETIC FLOWMETER | CI/FEP630/FEH630-EN REV. D
51
Menu
Easy Setup
Exit
Select
5.
Use
/
to select ‘Easy Setup’.
6.
Confirm the selection with
.
Easy Setup
Language
Language
Next
Edit
7.
Use
to call up the edit mode.
8.
Use
/
to select the desired language.
9.
Confirm the selection with
.
Easy Setup
Unit Volumeflow Qv
l/s
Next
Edit
10.
Use
to call up the edit mode.
11.
Use
/
to select the desired unit for the volume flow
rate.
12.
Confirm the selection with
.
Easy Setup
Qv Max 1
25.000 l/s
Next
Edit
13.
Use
to call up the edit mode.
14.
Use
/
to set the desired upper range value.
15.
Confirm the selection with
.
The device is factory calibrated to the flow range end value
Q
max
DN, unless other customer information is available. The
ideal upper range values are those which correspond to a flow
velocity of 2 to 3 m/s (0.2 to 0.3 × Q
max
DN)
The adjustable upper range values are listed in the table at
Measuring range table
on page 54.
Easy Setup
Unit Vol. Totalizer
l/s
Next
Edit
16.
Use
to call up the edit mode.
17.
Use
/
to select the desired unit for the volume
totalizer.
18.
Confirm the selection with
.
Easy Setup
Pulses per Unit
10.000/m³
Next
Edit
19.
Use
to call up the edit mode.
20.
Use
/
to select the desired pulse per unit for the
pulse output.
21.
Confirm the selection with
.