FEP630, FEH630
ELECTROMAGNETIC FLOWMETER | CI/FEP630/FEH630-EN REV. D
33
Digital output 41 / 42, 51 / 52
Can be configured as pulse, frequency or binary output via on-
site software.
G11597-02
A
16...30 V DC
B
R
B
U
CE
I
CE
R
B
U
CE
I
CE
41+
51+
I
E
42-/
52-
41+
51+
I
E
42-/
52-
R
B
R
B
012345
16...30 V
D
C
012345
R
B
A
Digital output 41 / 42, 51 / 52 passive as a pulse or frequency output
B
Passive digital output 51 / 52 as binary output
Figure 43: (I = internal, E = external, RB = load)
Pulse / frequency output (passive)
Terminals
41 / 42, 51 / 52
Output ‘closed’
0 V
á
U
CEL
á
3 V
For f < 2.5 kHz: 2 mA < I
CEL
< 30 mA
For f > 2.5 kHz: 10 mA < I
CEL
< 30 mA
Output ‘open’
16 V
á
U
CEH
á
30 V DC
0 mA
á
I
CEH
á
0.2 mA
f
max
10.5
kHz
Pulse width
0.1 to 2000 ms
Binary output (passive)
Terminals
41 / 42, 51 / 52
Output ‘closed’
0 V
á
U
CEL
á
3 V
2 mA
á
I
CEL
á
30 mA
Output ‘open’
16 V
á
U
CEH
á
30 V DC
0 mA
á
I
CEH
á
0.2 mA
Switching function
Parameterization possible.
Note
• Terminals 42 / 52 have the same potential. Digital outputs
DO 41 / 42 and DO 51 / 52 are not electrically isolated from
each other. If an additional electrically isolated digital output
is required, a corresponding plug-in module must be used.
• If you are using a mechanical counter, we recommend setting
a pulse width of
â
30 ms and a maximum frequency of
f
max
á
30 Hz.
Current output V1 / V2, V3 / V4 (plug-in module)
Up to two additional plug-in modules can be implemented via
the ‘Passive current output (red)’ option module.
G11897-02
A
B
V1+
I
E
V2-
R
B
O
C
1
V3+
I
E
V4-
R
B
O
C
2
A
Current output V1 / V2, passive
B
Current output V3 / V4, passive
Figure 44: (I = internal, E = external, RB = load)
The plug-in module can be used in slot OC1
and
OC2.
G10323-02
0
0
100
200
300
400
500
600
5
10
15
20
25
30
35
RB
[Ω]
Uq [V]
Permissible source voltage U
q
for passive outputs in relation to load
resistance R
B
where Imax = 22 mA.
JJJ
= Permissible range
Figure 45: Source voltage for passive outputs
Passive current output
Terminals
V1 / V2, V3 / V4
Output signal
4 to 20 mA
Load R
B
250
έ
á
R
B
á
600
έ
Source voltage U
q
* 13
V
á
U
q
á
30 V
Measuring error
< 0.1 % of measured value
Resolution 0.4
μ
A per digit
* The source voltage U
q
is dependent of the load R
B
and must be placed in
an additional area.