25
USER M A N UA L
16: Floating charger voltage adjustment
Interface
Settings
Parameter 2:
you may choose Add or Sub to adjust floating charger
voltage.
Parameter 3:
the voltage range is from 0V to 8V, the default value is 0V.
17: Constant charger voltage adjustment
Interface
Settings
Parameter 2:
you may choose Add or Sub to adjust constant charger
voltage.
Parameter 3:
the voltage range is from 0V to 4V, the default value is 0V.
18: Maximum charger current setting
Interface
Settings
Parameter 3:
The maximum charging current could be adjusted.
Default value is 4A for long run model and 1A for standard model.
The available options are 1A, 2A, 4A and 6A.
6A is only available for the UPS with 16 pieces of batteries.
19: Battery capacity and groups setting
Interface
Settings
Parameter 2:
Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH, 26AH,
40AH, 65AH, 100AH and so on.
The default value is 9AH.
Parameter 3:
Set battery group range from 1 to 6.
The default value is 1 group.
These parameters are for the battery backup time calculation.
20: Bypass mode setting
Interface
Settings
Parameter 3:
Calibrate the displayed backup time by adjusting this multiplier factor.
The formulation is listed below:
Displayed backup time=Original calculated backup time x multiplier factor
The default value of multiplier factor is 1.0 and the setting range is from
0.5 to 2.