POWERVALUE 11T IN —
6-10 KVA
3 .3 Single UPS installation
Installation and wiring must be performed in
accordance with the local electric laws/
regulations and execute the following
instructions by professional personnel.
1) Make sure the mains wire and breakers in the
building are in compliance with the standard
of rated capacity of UPS to avoid the hazards
of electric shock or fire.
NOTE!
Do not use the wall receptacle as
the input power source for the UPS,
as its rated current is less than the
UPS' maximum input current.
Otherwise, the receptacle may be
burned and destroyed.
2) Switch off the mains switch in the building,
before installation.
3) Turn off all the connected devices before
connecting to the UPS.
4) Prepare wires based on the following table:
Model
Wiring spec (AWG)
Input
Output
Battery
Ground
6KB
10
12
12
6KS
10
12
12
12
10KB
8
8
8
10KS
8
8
8
8
NOTE!
It is recommended to use suitable
wire in above table or thicker for
safety and efficiency.
NOTE!
The selections for color of wires
should be followed by the local
electrical laws and regulations.
5) Cabinet placement: Secure the UPS to the
ground with two shipping brackets A by fixing
four screws as shown below chart.
6) Remove the cable gland cover on the rear
panel of UPS. Then connect the wires
according to the following terminal block
diagrams: (Connect the earth wire first when
making wire connection. Disconnect the earth
wire last when making wire disconnection!)
NOTE!
Make sure that the wires are
connected tightly with the
terminals.
NOTE!
Please install the output breaker
between the output terminal and
the load, and the breaker should be
qualified with leakage current
protective function if necessary.