20   PowerValue 11 RT 6-10kVA

 | User manual

3.5  Initial startup 

CAUTION

SWITCH OFF THE CONNECTED LOADS BEFORE 
TURNING ON THE UPS.  SWITCH ON THE LOADS 
ONE BY ONE AFTER THE UPS IS TURNED ON.  

SWITCH OFF ALL OF THE CONNECTED LOADS 
BEFORE TURNING OFF THE UPS.

To start up the UPS:
1.  Verify that the total equipment rating does not exceed the 

UPS capacity.

2.  Check that all cables are connected correctly and well-

fixed mechanically. 

3.  Set the upstream circuit breaker (not included) to the 

“power-on” position (ON). The UPS LCD panel will 
illuminate and show a welcome screen.

4.  The UPS transfers to bypass-mode.
5.  Keep the power-on button 

 on the UPS LCD panel 

pressed for at least three seconds.

6.  Check the UPS display for active alarms or notices. 

Solve any active alarms. For more information, see 
“Troubleshooting” in Chapter 6.

7.  Verify that the UPS is operating normally and that the 

loads are powered.

8.  Adjust the date and time settings. For more information, 

see Chapter 4.4.2.5

NOTE

AT THE INITIAL STARTUP, THE UPS SETS THE 
SYSTEM FREQUENCY ACCORDING TO THE 
FREQUENCY IN THE INPUT LINE (INPUT 
FREQUENCY AUTO-SENSING IS ENABLED BY 
DEFAULT). AFTER INITIAL STARTUP, AUTO-
SENSING IS DISABLED UNTIL MANUALLY 
RE-ENABLED THROUGH THE OUTPUT 
FREQUENCY SETTINGS.

NOTE

AT INITIAL STARTUP, THE INPUT VOLTAGE AUTO-
SENSING IS DISABLED BY DEFAULT. AFTER 
MANUALLY ENABLED IN THE VOLTAGE 
SETTINGS, THE UPS OUTPUT VOLTAGE WILL BE 
SET ACCORDINGLY TO THE INPUT VOLTAGE. 
AFTER A SUBSEQUENT STARTUP, AUTO-
SENSING WILL BE DISABLED UNTIL MANUALLY 
RE-ENABLED IN THE OUTPUT VOLTAGE 
SETTINGS.

9.  If you connect the REPO port, test this function by 

activating the external REPO switch and verifying that its 
status changes on the UPS display.

3.6  Emergency power off (EPO)

The EPO connector can be used to block the output of the 
UPS in case of an emergency. The EPO connector can be 
configured as Normally closed (NC) or Normally opened (NO) 
through the USB or RS232 port.

By default, the EPO connector is Normally closed (NC) by a 
jumper in the rear panel. If the jumper is removed, the UPS 
output will not supply energy to the load until the EPO status 
is changed.

Enable  the  EPO  status       

Disable the EPO status

Figure 26: EPO connector

To return to normal status, the EPO connector must be 
closed. Enter the LCD menu to clear the EPO status (for more 
information, see Chapter 4.4.2.3). The UPS alarm is cleared 
and bypass mode is recovered. Set the UPS to inverter mode 
manually.

Содержание PowerValue 11 RT

Страница 1: ...l un I Jet _________ __ ABB Powervalue 11 RT 6 10 https www uni jet com catalog istochniki besperebojnogo pitaniya on line ibp 1 kva 10kva abb powervalue 11 rt html...

Страница 2: ...PowerValue 11 RT 6 10 kVA User manual...

Страница 3: ...RESULT IN MINOR INJURY AND OR DAMAGE TO THE PRODUCT NOTE NOTE INDICATES THE PRESENCE OF A HAZARD WHICH COULD LEAD TO PROPERTY DAMAGE SAFETY WARNING THE SYMBOL IS USED TO ALERT THE USER TO WARNINGS CAU...

Страница 4: ...characteristics 12 3 4 Electrical installation 14 3 5 Initial startup 20 3 6 Emergency power off EPO 20 3 7 Paralleling the units 21 3 8 Installation Checklist 24 4 Operation 25 4 1 Control Panel 25...

Страница 5: ...4 PowerValue 11 RT 6 10kVA User manual...

Страница 6: ...AREA TO WARN ELECTRICAL MAINTENANCE PERSONNELS THAT THE CIRCUIT FEEDS A UPS MAKE SURE THAT WARNING LABEL CONTAINS THE FOLLOWING TEXT OR EQUIVALENT ISOLATE THE UPS UNINTERRUPTIBLE POWER SUPPLY BEFORE...

Страница 7: ...FIRE AS THEY MAY EXPLODE WARNING DO NOT OPEN OR MUTILATE THE BATTERIES WARNING RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES 1 3 Declaration of Safety conformity and CE marking PowerValue 11 RT...

Страница 8: ...ISCONNECT THE BATTERIES BEFORE CARRYING OUT ANY KIND OF SERVICE AND OR MAINTENANCE VERIFY THAT NO CURRENT IS PRESENT AND NO HAZARDOUS VOLTAGE EXISTS IN THE CAPACITOR OR BUS CAPACITOR TERMINALS WARNING...

Страница 9: ...or supplier immediately in case of any damage 3 1 3 Storage of UPS If you plan to store the UPS prior to use keep the UPS in a dry clean and cool storage room with an ambient temperature between 15 C...

Страница 10: ...de the cabinet into the rack as shown in Figure 1 Figure 1 Rack mount installation If installing additional UPS units repeat the steps above for each cabinet 3 2 2 1 Connecting the external battery mo...

Страница 11: ...owerValue 11 RT 10kVA To connect the external battery modules 1 Plug the battery module cable into the UPS battery connector in the rear panel of the UPS as shown in Figure 3 3 2 2 2 Standalone Tower...

Страница 12: ...al tower position 1 Carefully rotate the LCD control panel 90 to the right in the top and bottom front panels as shown in Figure 6 Figure 6 Display rotation 2 Place the units to a vertical position 3...

Страница 13: ...tton Scroll Button Down or Forward 3 3 2 Rear panel Table 2 and Figures 9 and Table 3 and Figure 10 show the connectors and ports in the UPS rear panel 1 GND contact 2 EPO 3 Parallel port 4 Output cir...

Страница 14: ...werValue 11 RT 10 kVA rear view 1 SNMP AS400 slot 2 EPO 3 USB 4 Parallel port 5 Battery connector 6 GND contact 7 Output sockets 8 Output circuit breaker 9 AC output 10 Bypass 11 AC input Table 3 Powe...

Страница 15: ...ontactor 208 240V 35A PowerValue 11 RT 6 kVA 208 240V 50A PowerValue 11 RT 10 kVA Line input Neutral Input main breaker AC Contactor Mains Input Coil Remote Switch 3 4 2 Recommended cable sections and...

Страница 16: ...0kVA 15 3 4 3 Connections To access the terminal blocks remove the 2 screws from the terminal block cover as shown in Figures 12 and 13 Figure 12 PowerValue 11 RT 6 kVA Terminal block Figure 13 PowerV...

Страница 17: ...d Main low voltage switchboard MLVS CAUTION MAKE SURE THAT THE EARTH WIRE IS CONNECTED To connect the UPS cables 1 Connect a jumper between terminals JP and L 2 Connect the input and output cables Use...

Страница 18: ...erent a transformer should be connected to the inputs Figure 18 Figure 19 and Figure 20 show the alternative ways of connecting the inputs to the transformers Figure 17 UPS Diagram with Dual Input Fee...

Страница 19: ...THAT THE EARTH WIRE IS CONNECTED To connect the UPS cables 1 Ensure that the jumper JP is disconnected 2 Connect the input output and bypass cables Use appropriate tools and terminal splices to ensure...

Страница 20: ...verter Main low voltage switchboard MLVS Normal AC Load Figure 24 Frequency converter connections for 6kVA units Figure 25 Frequency converter connections for 10kVA units CAUTION INDUCTIVE LOADS FOR E...

Страница 21: ...ABLED BY DEFAULT AFTER INITIAL STARTUP AUTO SENSING IS DISABLED UNTIL MANUALLY RE ENABLED THROUGH THE OUTPUT FREQUENCY SETTINGS NOTE AT INITIAL STARTUP THE INPUT VOLTAGE AUTO SENSING IS DISABLED BY DE...

Страница 22: ...eaker panel is lower than 10 meters the length difference between input and output cables of the UPS must be lower than 20 When the distance between the UPS in parallel and the breaker panel is more t...

Страница 23: ...between the two UPS units is lower than 0 5V If the output voltage difference is higher than 0 5V the UPS voltage needs to be regulated If the output voltage difference is lower than 0 5V switch on t...

Страница 24: ...PS output breaker 9 Transfer the main maintenance switch or static switch from BPS to UPS 10 Press the power on button of one UPS and each UPS will turn on Both UPS will then work in parallel in onlin...

Страница 25: ...nated A ground conductor is properly installed Battery enclosure is installed Air conditioning equipment is installed and operating correctly The area around the installed UPS system is clean and dust...

Страница 26: ...software 4 1 Control Panel The user friendly control panel has two parts selection keys power management LCD display PMD 4 Operation Figure 29 Control panel Selection keys LCD display 4 1 1 Selection...

Страница 27: ...nutes Overload Beep twice every second Table 5 Definition of alarms Figure 30 The default LCD display Operating mode Battery information Mains input information UPS output information Load information...

Страница 28: ...ut from ECO mode to battery mode is 10ms and not recommended for sensitive loads Converter mode In converter mode the UPS runs with fixed output frequency 50Hz or 60Hz In case of a mains failure the U...

Страница 29: ...1 second and the UPS starts up 4 After a few seconds the UPS transfers to battery mode When the UPS is supplied with power from the mains the UPS transfers to online mode without interruption in the o...

Страница 30: ...Navigation Use the scroll buttons to navigate through the UPS screens From the main screen UPS status screen press or for information on alarm parallel system and battery From the main screen keep pre...

Страница 31: ...ent log Reset all the events from the log file No Yes No Restore factory settings Recover all settings in the LCD menu and the EPO polarity and locks the DC start up can be executed only when UPS is i...

Страница 32: ...lel system 1 UPS system Parallel system 4 4 2 4 Identification The identification menu shows the UPS serial number firmware serial number and model type Press to navigate through the Identification me...

Страница 33: ...s cut off enabled disabled disabled Redundancy lost in parallel UPS systems One of the parallel units has been disconnected from the system enable disabled enabled Bypass voltage low limit When the vo...

Страница 34: ...mode voltage low limit 5 218 5 5V ECO mode voltage high limit 5 241 5V ECO mode frequency low limit 5 47 5Hz ECO mode frequency high limit 5 52 5Hz External battery modules 0 Set running time LCD con...

Страница 35: ...34 PowerValue 11 RT 6 10kVA User manual...

Страница 36: ...ing control and firmware updates To establish communication between the UPS and a computer connect one end of the serial communication cable to the RS 232 port on the UPS and the other end to the RS 2...

Страница 37: ...NOT HAVE TO BE SHUTDOWN BEFORE INSTALLING A COMMUNICATION CARD To install a network management card 1 Remove the two screws that protect the communication slot of the UPS 2 Insert the SNMP card into...

Страница 38: ...sing the UPS status menu screen 1 Press for longer than 1 second to go to the UPS status menu screen 2 Press to access the UPS Status main screen 3 Press to access the notice and alarm screens 4 The U...

Страница 39: ...oft start successfully Contact your service representative Output Short Circuit Alarm Code 31 Indicates that the UPS has detected abnormally low impedance placed on its output considered as a short ci...

Страница 40: ...system is in redundant mode only the UPS with the failure will transfer to fault mode without output Other UPS will still support the load If the parallel system is not redundant and the load cannot...

Страница 41: ...40 PowerValue 11 RT 6 10kVA User manual...

Страница 42: ...Webserver Modbus 97 Output Load Percentage Output Webserver Modbus 100 Battery Voltage V Battery Webserver Modbus 110 Battery Capacity Battery Webserver Modbus 103 Temperature C Environmental Webserve...

Страница 43: ...toring UPS Status Battery Status Battery status UPS Monitoring UPS Status Capacity Battery measurement UPS Monitoring UPS Status Voltage Battery measurement UPS Monitoring UPS Status Time on Battery B...

Страница 44: ...or PowerValue 11 RT 10 kVA 1 x 20 x 9 0Ah Standard EBM value setting through LCD display and RS232 M is the total nr of standard EBM connected M 1 UPS Model LCD display path Settings Password USER Ext...

Страница 45: ...614 00798 03 Contact us Copyright ABB All rights reserved Specification subjects to change without notice www abb com ups ups sales ch abb com...

Отзывы: