The quiescent bus potential is fixed with the resistors R
d
, R
t
und
R
u
.
R
d
= 390
Ω
R
t
= 150
Ω
R
u
= 390
Ω
Wiring should take place in accordance with Fig. 3. The resistors
R
d
, R
t
and R
u
should be installed in the 9-pin bus connector in
such way that the recorder can be separated from the bus with
the bus remaining closed.
Fig. 3
Bus end wiring
Z-17340
Data formats
The data to be transmitted can be formatted in four different
ways:
− Type BYTE
Value range 0...255
− Type CHAR
Value range −128...+127
− Type WORD
Value range 0...65535
− Type FLOAT
Value range
±
1.175494E−38..
±
3.38
BYTE
The BYTE format is used for the selection of parameters from
the tables in the “Parameter” section.
CHAR
The CHAR format is used when ASCII characters are
transmitted. Hex-codes must be used.
WORD
The WORD format consists of 2 bytes and is used when
integers are to be transmitted without preceding signs (integer
values). During transmission, high bytes precede low bytes.
For example: The value 820 should be transmitted.
820 dec = 03 34 hex
4
Technical Data... • Data formats