![ABB PointMaster 200 Series Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/abb/pointmaster-200-series/pointmaster-200-series_operating-manual_3941951021.webp)
0019H
Byte
Status of DI binary inputs via
IO converter
Bit
0 DI 7
1 DI 8
2 DI 9
3 DI 10
4 DI 11
5 DI 12
6 DI 13
7 DI 14
001AH
Byte
Status of DO binary outputs on
the recorder
Bit
0 DO 1
1 DO 2
2 DO 3
3 DO 4
4 DO 5
5 DO 6
6 DO xx
7 DO xx
001BH
Word
Status of DO binary outputs
via IO converter
Bit
0 DO 7
1 DO 8
2 DO 9
3 DO 10
4 DO 11
5 DO 12
6 DO 13
7 D0 14
8 DO 15
9 DO 16
A DO 17
B DO 18
C DO 19
D D0 20
001DH
D-Word
Device alarm status
Bit
00
01 CPU error
02 Internal RAM error
03 External RAM error on CPU card
04 Communication error between CPU and
clock
05 A/D converter error
06 Check sum error, parameter data CPU
card
07 Reading error with EEPROM on CPU
card
08 Writing error with EEPROM CPU card
09 Check sum error, calibration data channel
card
0A Reading error with EEPROM on channel
card
0B Writing error with EEPROM channel card
0C Watchdog generates device reset
0D Printer queue full
0E Print head stuck
0F Voltage interruption to clock module
10 Speed too high for text output
11 Oscillator watchdog generates device
reset
12 Communication error with IO converter
13 Check sum error F-RAM
14 Reading error with F-RAM
15 Writing error with F-RAM
16 Error, reference junction correction
0021H
D-Word
Device alarm:
acknowledgment status
as for device alarm status
Parameters