MOTOR I ZE D CH A NG E - OV E R A N D TR A N S FE R SWITCH E S , OTM _C

M OTO R IZED C H A N G E- OV ER A N D T R A N SFER S W I TC H E S , OT M _ C

Electrical operation is prevented when the handle is attached to the switch panel.

Figure 8.6 

Attaching the handle

3.

   Operate the motorized change-over switch by turning the handle to the required position (I, 0, II).

You can operate the motorized change-over switch manually by using the handle that is included in the 
delivery. To operate the motorized change-over switch manually:

1. 

  Turn the Motor/Manual selector to the Manual (Man.) position, see Figure 8.5. The motor operator 

 

is switched off and electrical operation is prevented.

Figure 8.5 

Motor/Manual selection in the Man. position

2.

   Attach the handle by pressing it to the switch panel until it clicks into place. You can attach

 

the handle in all positions (I, 0, II), see Figure 8.6.

A0413

4

M

M

Man.

Man.

M

M

A04135

II

I

M

M

Man.

Man.

M

M

Man.

Man.

CLICK !

8.2  Manual operation by using the handle

Information

Содержание OTM C Series

Страница 1: ... INSTALL ATION AND OPER ATING INSTRUCTION Motorized change over and transfer switches OTM_C Motorized change over and transfer switches 34OTM C rev G 1SCC303002M0206 ...

Страница 2: ...ostitions 19 6 2 Labelling 19 7 Connecting 20 8 Operating 21 8 1 Electrical operation 21 22 8 1 1 Impulse control 23 8 1 2 Continuous control 24 8 2 Manual operation by using the handle 25 8 3 Locking 26 8 3 1 Locking the electrical operation 26 8 3 2 Locking the manual operation 26 27 9 Technical data 28 29 10 Accessories 30 10 1 Terminal clamp sets OZXA_OTZB_ 30 10 2 Bridging bars OTZC_ OTZR_ 31...

Страница 3: ...ITCHES OTM _C Operation OTM_C Operation 0 I 0 0 II Switch Close Open Close Open Switch Switch Switch Operation I II I Close Open Close Open ON OFF ON ON ON O N ON ON O FF OTM_CF Switch Switch Close Open Close Open 0 I 0 0 II Operation OTM_CL ...

Страница 4: ...ging bars the type name accessories OTS_ Terminal shrouds the type name accessories OA_ Auxiliary contacts the type name accessories ODPS_ Dual power source the type name accessories Caution provides important information or warns about a situation that may have a detrimental effect on equipment General warning warns about a situation where something other than electrical equipment may cause physi...

Страница 5: ...he change over switch and the motor operator Figure 2 1 Motorized change over switch type OTM_C 1 Change over switch 2 Motor operator 3 Switch panel the operating mechanism 4 Handle for manual operation double grip handle in sizes OTM1000 3200_C 5 Motor Manual selection 6 Terminals for motor operator voltage supply 7 Terminals for push buttons 8 Fuse F1 of motor operator 9 Locking latch for releas...

Страница 6: ... over switch electrically remote control To operate the motorized change over switch electrically 1 Remove the handle from the switch panel You can remove the handle in all positions I 0 II 2 Turn the Motor Manual selector to the Motor M position to enable electrical operation I I I M M Man Man M M Man Man A04122 M M Man Man I I I M M Man Man M M Man Man Figure 3 1 Operating the motorized change o...

Страница 7: ...trical operation lock the locking latch with a padlock After the locking latch has been locked the motorized change over switch cannot be operated electrically You can lock electrical operation in all positions I 0 II Figure 3 2 Locking electrical operation A04136 I I I M M Man Man M M Man Man 1 2 5 6 mm ...

Страница 8: ...orized change over switch manually local operation To operate the motorized change over switch manually 1 Turn the Motor Manual selector to the Manual Man position to enable manual operation and to prevent electrical operation 2 Attach the handle to the switch panel You can attach the handle in all positions I 0 II Figure 3 3 Operating the motorized change over switch manually I I I M M Man Man A0...

Страница 9: ...NSFER SWITCHES OTM _C 4 Installation 4 1 Mounting the motorized change over switch Figure 4 1 An example of using protection against direct contact Use protection against direct contact Caution I I M M Man Man M M Man Man OMD A04126 I ...

Страница 10: ...3 U4 OTM400_C_M E4 E3 OTM315 400_C_M A1 293 116 116 258 A2 282 116 325 116 E3 E4 OTM160 250_WC_M E4 E3 OTM160 250_C_M 282 11 10 116 4 57 325 12 80 116 4 57 U3 U4 OTM200_C_M I A1 740 5 230 230 614 5 A2 E4 E3 OTM2000 2500_C_M A1 556 5 230 230 476 5 A2 476 5 230 556 5 230 E3 E4 OTM1600_WC_M E4 E3 OTM1000 1250_C_M 476 5 18 77 230 9 06 556 5 21 92 230 9 06 U3 U4 OTM800 1200_C_M OTM600 800E_C_ OTM160 25...

Страница 11: ...00111 9 0 134 5 127 A2 20 65 A1 130 162 A B 25 122 130 150 87 5 3 23 160 48 5 72 25 37 20 83 65 E3 E4 14 100 E2 35 116 223 238 35 116 258 273 35 116 293 308 A A1 A2 B OTM160 250_C_M 9 0 134 5 127 65 A2 20 A1 130 A B 25 170 122 150 130 87 5 3 23 160 25 83 65 E3 E4 14 M00115 37 20 48 5 72 100 170 E2 43 116 239 254 43 116 282 297 43 116 325 340 66 A A1 A2 B OTM160 250_WC_M ...

Страница 12: ... 5 00 65 2 56 A2 20 0 79 A1 130 5 12 A B 25 0 98 170 6 69 122 4 80 150 5 91 130 5 12 87 5 3 44 23 0 91 3 0 12 160 6 30 25 0 98 83 35 5 3 27 1 40 65 2 56 U3 U4 14 0 55 M00112 37 1 46 20 0 79 48 5 19 09 72 2 83 100 3 94 170 6 69 U2 43 1 69 116 4 57 239 9 40 254 10 43 1 69 116 4 57 282 11 10 297 11 69 43 1 69 116 4 57 325 12 80 340 13 39 66 2 6 A A1 A2 B OTM200_C_M Figure 5 3 OTM200U_C_M Figure 5 4 O...

Страница 13: ...2 03 95 3 74 17 0 67 185 7 28 U2 54 2 13 142 5 59 281 11 06 299 11 77 54 2 13 142 5 59 335 13 19 353 13 90 54 2 13 142 5 59 389 15 31 407 16 02 146 5 75 81 3 19 A A1 A2 B OTM400_C_M M00116 137 25 A2 95 25 A1 156 120 A B OTM 315 400_WC_M E3 E4 54 54 142 142 334 5 353 407 11 220 160 150 31 25 195 25 4 56 87 192 43 20 5 32 5 126 51 5 95 17 185 388 5 A A1 A2 B Figure 5 6 OTM400U_C_M Figure 5 5 OTM315 ...

Страница 14: ...6 65 2 56 65 2 56 180 7 09 180 7 09 180 7 09 325 12 8 390 15 35 455 17 91 346 13 62 411 16 18 476 18 74 M00139 158 6 22 20 5 0 8 A A1 A2 B U2 U3 U4 OTM600_C_M 145 17 200 160 A1 147 5 A2 198 210 250 212 5 A B 47 5 39 45 132 6 110 5 5 64 1 256 E2 E3 E4 65 65 65 180 180 180 325 390 455 346 411 476 138 6 61 5 13 5 M00140 158 43 20 5 A A1 A2 B OTM630 800E_C_M Figure 5 8 OTM600U_C_M mm mm Dimension draw...

Страница 15: ... E3 80 230 476 5 506 5 E4 80 230 556 5 586 5 M00258 167 158 5 127 100 335 M Man 13 5 50 A2 200 186 171 260 A1 206 253 A B 63 306 272 250 74 5 15 136 50 400 15 19 296 5 75 OTM1000 1250_C_M A A1 A2 B E2 80 230 396 5 426 5 E3 80 230 476 5 506 5 E4 80 230 556 5 586 5 167 158 5 M00256 80 127 100 335 mm Figure 5 9 OTM1000 1200E_C_M mm Figure 5 10 OTM1600E_C_M Dimension drawings OTM1000 1200E_C_M OTM1600...

Страница 16: ... 12 84 258 10 16 246 9 69 OTM800 1200_C_M A A1 A2 B U2 80 3 15 230 9 06 396 5 15 62 426 5 16 8 U3 80 3 15 230 9 06 476 5 18 77 506 5 19 96 U4 80 3 15 230 9 06 556 5 21 92 586 5 23 11 M00257 400 15 76 15 0 59 19 0 75 1 2 2 1 296 5 11 68 75 2 95 1 2 136 5 36 74 5 2 93 15 0 59 83 3 27 405 15 96 1 2 167 6 58 335 13 19 Figure 5 11 OTM800 1200U_C_M mm in Dimension drawings OTM800 1200U_C_M ...

Страница 17: ... 5 770 5 M00259 296 5 206 335 136 85 74 5 15 167 158 5 400 15 19 75 100 127 mm Figure 5 12 OTM2000 2500E_C_M 13 5 A2 200 100 186 171 280 A1 206 258 A B 73 284 296 364 376 410 325 61 4 8 85 63 15 191 Ø 400 15 245 141 156 5 223 429 170 5 100 5 377 424 240 M00432 E2 E3 E4 140 250 521 5 551 5 140 250 661 5 691 5 140 250 801 5 831 5 A A1 A2 B OTM3200_C_M mm Figure 5 13 OTM3200_C_M Dimension drawings OT...

Страница 18: ...18 MOTORIZED CHANGE OVER AND TR ANSFER SWITCHES OTM _C 6 Connections I I I 2 A06272 1 I I I 10 mm 10 mm 50 mm 50 mm Figure 6 1 Mounting the connections to the motorized change over switches OTM3200_C_M ...

Страница 19: ... change over switches are horizontal wall mounted or table mounted Figure 6 3 Labelling of the motorized change over switches Figure 6 2 Mounting positions A06103 6 2 Labelling I I M M Man Man M M Man Man I A04128 1 2 Information Do not install the motorized change over switches in any other position than those described above ...

Страница 20: ...uttons or selector switch 3 Terminal for state information of locking 7 1 Control circuit Do not couple power for the control terminal See the correct terminal for the power supply in Figure 7 1 The control voltage output C 24Vdc on the control terminal is non isolated see box 2 in Figure 7 1 When relay outputs are used with inductive loads such as relays contactors and motors they must be protect...

Страница 21: ...ned off Never handle control cables when the voltage of the motorized change over switch or external control circuits are connected Exercise sufficient caution when handling the unit Figure 8 1 Releasing the handle 8 1 Electrical operation The motorized change over switches are available for remote control To operate the motorized change over switch electrically 1 Release the handle from the switc...

Страница 22: ...under the motor operator Only use the same type of fuse that is described on the label close to the fuse Figure 8 2 Motor Manual selection switch in the Motor M position 3 Operate the motorized change over switch with the push buttons or selector switch via impulse control or continuous control 2 Turn the Motor Manual selection switch to the Motor M position see Figure 8 2 Information ...

Страница 23: ...ven to the corresponding position I 0 II The control impulse must last more than 100ms to take effect A new command cannot be given until the change over switch has reached the position of the previous command Figure 8 3 shows the operation of the change over switch with impulse control I position 0 position I II _CL II position I command II command 0 command 0 I II _CL I II 100 ms 100 ms 100 ms A...

Страница 24: ...usly When you press the control button the change over switch is driven to the corresponding position I 0 II Oper ation of position 0 will over run control of the other positions that is if you simultaneously give the 0 command with another command the change over switch is driven to position 0 Figure 8 4 shows the operation of the change over switch with continuous control Figure 8 4 Continuous c...

Страница 25: ... is included in the delivery To operate the motorized change over switch manually 1 Turn the Motor Manual selector to the Manual Man position see Figure 8 5 The motor operator is switched off and electrical operation is prevented Figure 8 5 Motor Manual selection in the Man position 2 Attach the handle by pressing it to the switch panel until it clicks into place You can attach the handle in all p...

Страница 26: ...k the electrical operation in all positions I 0 II To lock electrical operation 1 Pull up the locking latch under the change over switch panel 2 Place the padlock under the latch see Figure 8 7 The handle cannot be attached when electrical operation is locked 8 3 2 Locking the manual operation By default manual operation can only be locked to position 0 Locking to position I and II is optional and...

Страница 27: ...ndle cannot be removed when padlocked to position 0 The following figure shows the locking state information the voltage on motor operator supply needed A04144 M M Man Man M M Man Man Man M M Man Man M 14 12 11 23 24 23 24 23 24 23 24 23 24 23 24 11 12 14 11 12 14 11 12 14 11 12 14 11 12 14 I I I M M Man Man M M Man Man A04137 Information ...

Страница 28: ...Table 7 2 Protection degree IP 20 front panel Rated impulse withstand voltage Uimp 4 kV Voltage supply PE N L 1 5 2 5 mm2 F2 Max MCB 16 A Cable of the push buttons no SELV C II I 0 1 5 2 5 mm2 Maximum cable length 100 m State information of locking no SELV Handle attached or motor operator locked 11 12 14 C O 1 5 2 5 mm2 Locking motor operator 23 24 NO 1 5 2 5 mm2 Operating temperature 25 55 C Tra...

Страница 29: ... 2 6 8 4 0 6 1 6 1 2 3 0 0 6 1 6 T 2 5 AH OTM600 800_C 24 Vdc 4 0 22 4 0 5 1 5 1 1 2 5 0 5 1 5 T 5 AH OTM1000 1600_C 220 240 Vac 1 8 7 7 0 5 1 5 1 5 3 0 0 5 1 5 T 2 AH OTM1000 1600_C 110 125 Vac dc 3 0 13 3 0 5 1 5 1 5 3 0 0 5 1 5 T 4 AH OTM1000 1600_C 48 Vdc 5 3 22 4 0 5 1 5 1 5 3 0 0 5 1 5 T 5 AH OTM1000 1600_C 24 Vdc 8 0 26 6 1 0 2 0 2 0 3 5 0 8 1 7 T 10 AH OTM2000 2500_C 220 240 Vac 1 8 7 7 0 ...

Страница 30: ...B9 OTM400U_C_ OZXA 400_ OZXA 406_ OTM160 OTM250E_C_ OZXB1L OZXB2 OZXB2L OZXB8 OZXB9 OTM200U_C_ OZXA 200_ OZXA 206_ A04138 OTM1000 1600E_C_ OZXB3 OZXB4 OZXB5 OZXB6 OZXB7L max 1 pcs side OTM800 1200U_C_ OZXA 1200_ OZXA 1206_ OTM2000 2500E_C_ OTM3200E_C_ OZXB3 OZXB4 OZXB5 OZXB6 OZXB7L 10 Accessories 10 1 Terminal clamp sets OZXA_ OZXB_ Figure 10 1 Mounting of the terminal clamp sets types OZXB_ and O...

Страница 31: ... Figure 10 2 Mounting of the bridging bars type OTZC_ to the motorized change over switches OTM160 800E_C_ 10 2 Bridging bars OTZC_ OTZR_ OTZC_ OTZC13 OTZC14 OTM160 250_C_ OTZC23 OTZC24 OTM315 400_C_ OTZC33 OTZC34 OTM600 800_C_ 630 A 800 A A04139 1 2 3 I I ...

Страница 32: ...ER SWITCHES OTM _C Figure 10 3 Mounting of the bridging bars type OTZC_ to the motorized change over switches OTM1000 1600E_C_ and OTM800 1200U_C_ A04189 OTZC_ II 2 1 3 OTZC43 OTZC44 OTM1000 1250E_C OTZC53 OTZC54 OTM1600E_C OTM800 1200U_C ...

Страница 33: ...IZED CHANGE OVER AND TR ANSFER SWITCHES OTM _C Figure 10 4 Mounting of the bridging bars type OTZC_ to the motorized change over switches OTM2000 2500E_C_ A04190 I I I OTZC_ 3 1 2 OTZC63 OTZC64 OTM2000 2500_C_ ...

Страница 34: ...34 MOTORIZED CHANGE OVER AND TR ANSFER SWITCHES OTM _C Figure 10 5 Mounting of the bridging bars type OTZC_ to the motorized change over switches OTM3200E_C_ 2 OTM3200E_C_ I I I OTZC_ 1 3 OTZC73 OTZC74 ...

Страница 35: ...nting of the voltage sensing connectors type OMZB_ 10 3 Voltage sensing connectors OMZB_ A06123 OMZB1_ 6 3x0 8 2 3 1 OT630 800E_C_ OMZB3_ 6 3x0 8 OT1000 2500E_C_ OT800U_C_ CLICK I I 6 3x0 8 1 4 OT600U_C_ I OMZB4_ OT3200E_C_ 2 3 4 1 b a 2 3 OT315 400_C_ OT160 250_C_ OMZB2_ ...

Страница 36: ... motorized change over switches OTM160 800E_C_ OTM160 250_C_ OTM315 400_C_ OTM600 800_C_ OTS250_ OTS400_ OTS800_ M8 15 22 Nm 5 6 DIA in 133 195 lb in M10 30 44 Nm 266 390 lb in M12 50 75 Nm 433 664 lb in M M M M OTS400 1S G T OTS250 1S G T OTS800 1S G T OTS400 1L G T OTS250 1L G T OTS800 1L G T 1 2 1 2 I I I OTS_ 1S G T OTS_ 1L G T 4 3 A04140 ...

Страница 37: ... 8 Mounting of the terminal shrouds type OTS_ to the motorized change over switches OTM1000 1600E_C_ and OTM800 1200U_C_ 4 3 I I I A04213 2 1 2 1 M12 50 75 Nm 443 664 lb in OTM2000 2500E_C_ M M OTM3200E_C_ OTS2500 1S G T OTS4000 1S G T OTS2500 1L G T OTS4000 1L G T ...

Страница 38: ...38 MOTORIZED CHANGE OVER AND TR ANSFER SWITCHES OTM _C 10 5 Reversing bars OTZR_ A04210 II I ON OFF ON OTZR_ OT_100 250_C_ OT315 400_C_ OT600 800_C_ OTZR1 OTZR2 OTZR3 2 1 3 ...

Страница 39: ...S OTM _C 10 6 Voltage sensing connectors OMZB_ A06123 OMZB1_ 6 3x0 8 2 3 1 OT630 800E_C_ OMZB3_ ON ON OFF 6 3x0 8 OT1000 2500E_C_ OT800U_C_ CLICK I I I I I 6 3x0 8 I 1 4 OT600U_C_ I OMZB4_ OT3200E_C_ 2 3 4 1 b a 2 3 OT315 400_C_ OT160 250_C_ OMZB2_ ...

Страница 40: ...I I I A04213 2 1 2 1 M12 50 75 Nm 443 664 lb in OTM2000 2500E_C_ M M OTM3200E_C_ OTS2500 1S G T OTS4000 1S G T OTS2500 1L G T OTS4000 1L G T Figure 10 9 Mounting of the terminal shrouds type OTS_ to the motorized change over switches OTM2000 2500_C_ OTM3200_C_ ...

Страница 41: ... Man M M A04141 11 37 21 13 II I Man Man M M 1 2 3 XXXXXX OA 1G10 OA 3G01 I I II II 11 12 13 14 21 22 23 24 11 12 13 14 21 22 23 24 I OA 1G10 OA 3G01 I I II II II I 0 II I 0 II OA 1G10 OA 3G01 11 12 13 14 21 22 23 24 11 12 13 14 21 22 23 24 I OA 1G10 OA 3G01 II OTM_C OTM_CF max 2 2 max 2 2 max 2 2 max 2 2 OTM_CL max 2 2 max 2 2 OTM_C OTM_CF OTM_CL ...

Страница 42: ...he dual power source type ODPSE230C Connection diagram ODPSE230C Figure 10 11 The dual power source type ODPS230 Connection diagram ODPS230 Fuse Fuse A06289 ODPS230 OTM_C C I I I 0 L N C I I I 0 PE N L LN1 L N L N LN2 ODPS A06290 L1 ODPSE230C OTM_C L2 N L1 L2 N F1 F2 L N PE 1 2 X12 X 11 1 2 1 2 X 13 ...

Страница 43: ...Man Sp are Fuse Sp are Fuse Spare Fuse Spare Fuse 80 36 OTVS1 20 OTVS2 31 M M Man Man M M Man Man Sp are Fuse Sp are Fuse Spare Fuse FUSE Spare Fuse Spare Fuse xxxxA xxxV Fus e 2 3 I I M M Man Man M M Man Man I Spare Fuse Spare Fuse 1B 1A 1 OTVS0 OTM160 250_C I I I M M Man Man 1 1A 1B I I M M Man Man I 3 2 80 36 20 50 15 OTVS1 OTM160 250_C OTVS2 OTM315 3200_C 10 9 Handle and spare fuse storage OTV...

Страница 44: ...alent volume Size current Height Width Depth OTMDC100_C 6 3 in 190 mm 19 in 490 mm 12 in 315 mm OTM200U_C 16 in 406 mm 12 in 305 mm 8 in 203 mm OTM400U_C 24 in 610 mm 14 in 356 mm 10 in 254 mm OTM600U_C 24 in 610 mm 28 in 700 mm 16 in 400 mm OTM800 1200U_C 48 in 1220 mm 24 in 610 mm 16 in 400 mm Size Current A B D C OT_100 1200U_C 0 0 5 in 13 mm 0 5 in 13 mm According to the UL1008 standard ...

Страница 45: ...C_ if the conductors are wider than 39 mm 1 54 in phase barrier 68838 on OTM800 1200U_C_ if the lugs are wider than 54 mm 2 13 in phase barrier 68912 Phase barriers 68912 must be used on motorized change over switches types OTM1000 2500_C_ if the voltage is 415 V Phase barriers CXBY69470 must be used on OTM3200E_C The types for the package of 6 barriers are 68838 OTB800 6C 68912 OTB1600 6C CXBY694...

Страница 46: ...he phase barriers M M Man Man M M Man Man 110 173 118 21 5 110 I I I I I I 170 100 127 167 127 21 5 M M Man Man Phase barrier type 68912 on OTM800U_C_ OTM1000 1600E_C_ OTM2000 2500E_C_ Phase barrier type 68838 on OTM600U_C A06274 I I I Phase barrier type CXBY69470 on OTM3200E_C_ 170 100 21 5 141 240 192 ...

Страница 47: ...47 MOTORIZED CHANGE OVER AND TR ANSFER SWITCHES OTM _C CZ CN DA DE EL EN ES ET FI FR HR HU IE IT LT LV MT NL NO PL PT RO RU SE SK SL BG ...

Страница 48: ... Contact us ABB Oy P O Box 622 FI 65101 Vaasa Finland abb com lowvoltage Copyright 2020 ABB All rights reserved Specifications subject to change without notice 34OTM C rev G 1SCC303002M0206 29 10 2020 ...

Отзывы: