37
1SCC303002M0204, rev. D
Installation and operating instructions, OTM_C
9. UL standard switches
Figure 9.1
Clearances per UL 98, minimum enclosure size or equivalent volume
OTM200U_C
Cable size
Cable size
AWG
C
MCM
C
4-3
100 mm/4 in
250
200 mm/8 in
2
100 mm/4 in
300
250 mm/10 in
1
100 mm/4 in
1/0
125 mm/5 in
2/0
150 mm/6 in
3/0-4/0
175 mm/7 in
OTM400U_C
Cable size
Cable size
AWG
C
MCM
C
2
100 mm/4 in
250
250 mm/8 in
1
100 mm/4 in
300
250 mm/10 in
1/0
125 mm/5 in
350
350 mm/12 in
2/0
150 mm/6 in
3/0-4/0
175 mm/7 in
OTM600-1200U_C
Cable size
Cable size
AWG
C
MCM
C
2
100 mm/4 in
250
200 mm/8 in
1
100 mm/4 in
300
250 mm/10 in
1/0
125 mm/5 in
350
300 mm/12 in
2/0
150 mm/6 in
400
330 mm/13 in
3/0-4/0
175 mm/7 in
500
356 mm/14 in
600
381 mm/15 in
Current
Height
Width
Depth
OTM200U_C
406 mm/16 in
305 mm/12 in
203 mm/8 in
OTM400U_C
610 mm/24 in
356 mm/14 in
254 mm/10 in
OTM600U_C
610 mm/24 in
700 mm/28 in
400 mm/16 in
OTM800-1200U_C
1220 mm/48 in
610 mm/24 in
400 mm/16 in
OTM1600U_C
1200 mm/47 in
750 mm/30 in
400 mm/16 in
A
B
D
OTM200-1600U_C
0
13 mm/0,5 in
13 mm/0,5 in
9. UL standard switches
OTM1600U_C
Cable size
MCM
C
250
200 mm/8 in
300
250 mm/10 in
350
300 mm/12 in
400
330 mm/13 in
500
356 mm/14 in
600
381 mm/15 in