background image

8

Diagnostics

Diagnostics

Diagnostic LED

There is one diagnostic LED on the OREL-01 module. If the OREL-01 
is properly installed, the green LED lights when the drive is powered up. 
If the LED does not light within 5 seconds after power-up, there is no 
communication with the drive.

Step down this column. 

If an item is TRUE, look to 

the RIGHT for suggestions. 

Corrective Action

The module connection may 

be damaged

Warning!

 Dangerous voltages are present 

on the connector. Power down before 

attempting to repair connector pins.

• Power down.
• Remove the module and check the condition of 

the pins in the 6-pin connector.

• Reconnect and retest.

The module may have failed. Replace the module.

Содержание OREL-01

Страница 1: ...DriveIT Low Voltage AC Drives User s Manual Relay Output Extension Module OREL 01 ...

Страница 2: ...ly high voltage when mains power is applied regardless of motor operation WARNING There can be dangerous voltages inside the drive from external control circuits even when the drive mains power is shut off Exercise appropriate care when working on the unit Neglecting these instructions can cause physical injury or death Use of Warnings and Notes There are two types of safety instructions throughou...

Страница 3: ... Contents Table of Contents Safety 2 Use of Warnings and Notes 2 Table of Contents 3 Installation 4 Preparing for Installation 4 Installing the Module 5 Start Up 7 Diagnostics 8 Diagnostic LED 8 Technical Data 9 ...

Страница 4: ...Module The Relay Output Extension module OREL is an interface for connecting three relay outputs to an ACS550 or ACH550 drive Module Layout Compatibility The OREL 01 is compatible with all ACS550 and ACH550 drives Green LED Warning Sticker Relay 4 Relay 5 Relay 6 X0051 ...

Страница 5: ...Remove the drive cover See instructions in the drive User s Manual 3 Insert the OREL 01 module s plastic hooks into the front of the drive at SLOT 1 4 Carefully fit the connector at the other end of the module into the drive connector 5 Press until the retaining clip locks the module into position NOTE Signal and power connections to the drive are automatically made through a 6 pin connector 6 Non...

Страница 6: ...ive s User s manual and replace the drive s cover Apply Power 1 Turn on the mains power to the drive Note When power is applied to the drive the LED on the OREL module should light 2 Continue with the next section Start Up Identification Hardware Description 1 RO4C RELAY OUTPUTS RO4 TO RO6 Max continuous current 2 A rms cos ϕ 1 1 A rms cos ϕ 0 4 Max switching capability 6 A 24 V DC resistive load ...

Страница 7: ...using the OREL 01 module 1 Power up the drive 2 Use the control panel on the drive and set the parameters for relay outputs 4 to 6 in Group 14 Relay Outputs Refer to the drive s User s Manual for parameter descriptions and for instruction on the control panel operation ...

Страница 8: ... there is no communication with the drive Step down this column If an item is TRUE look to the RIGHT for suggestions Corrective Action The module connection may be damaged Warning Dangerous voltages are present on the connector Power down before attempting to repair connector pins Power down Remove the module and check the condition of the pins in the 6 pin connector Reconnect and retest The modul...

Страница 9: ...losure Refer to the drive s rating Ambient Conditions The module is mounted inside the drive enclosure Refer to the drive s requirements Connectors Connectors on the module 6 pin connector Three 3 pin screw type non detachable terminal blocks that accept wire connectors up to 1 5 mm2 16 AWG Ref mm in H 9 2 0 4 L 46 4 1 8 W 36 2 1 4 X0053 ...

Страница 10: ...tandards EN 50081 2 and EN 50082 2 Relay Outputs The specifications for the module relay outputs are Max contact voltage 30 V DC 250 V AC Max switching capability 6 A 24 V DC resistive load 1500 VA 250 V AC Max continuous current 2 A rms cos ϕ 1 1 A rms cos ϕ 0 4 Minimum current 10 mA 12 V DC Contact material Silver nickel AgN Isolation between relay digital outputs test voltage 2 5 kV rms 1 minut...

Страница 11: ......

Страница 12: ...ephone 358 10 22 11 Telefax 358 10 22 22681 Internet http www abb com ABB Inc Drives and Power Electronics 16250 West Glendale Drive New Berlin WI 53151 USA Telephone 262 785 3200 800 243 4384 Telefax 262 780 5135 3AUA0000001935 REV A EN EFFECTIVE April 15 2003 ...

Отзывы: