Chapter 7 – Fault Tracing
NMBA-01 Installation and Start-up Guide
7-3
Table 7-2 Modbus Error Codes during Operation.
Flash Code
Status
Correction
Occasional flash
on Error LED
Module on-line.
Parity, CRC or unsupport-
ed command received.
Check the wiring and earthing of
the module.
Verify that only supported com-
mands are sent to the module.
Error LED flashes
continuously
NMBA is OK, no response
from the drive on fibre link.
Power on the drive.
Check the fibre link wiring.
All LEDs flash con-
tinuously at the
same time.
Watchdog time out.
Hardware failure on NMBA mod-
ule. Switch power off and wait a
few seconds before switching the
power on again; if the problem
persists, check that fieldbus pa-
rameter
02 MODBUS MODE is
set to RTU wdg:rst.
Continuous reboot.
Fast blinking of
ER-
ROR LED for ap-
prox. 2 sec.
repeated every few
sec.
Drive configuration write
failed (DDCS link commu-
nication fault).
Check fibre optics, DDCS channel
and SW version of the drive.