![ABB NMBA-01 Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/abb/nmba-01/nmba-01_installation-and-startup-manual_2753025.webp)
NMBA-01 Installation and Start-up Guide
6-1
Chapter 6 – Communication
Overview
This chapter describes the Modbus communication with the drive.
Register Read
and Write
The drive parameter and data set information is mapped into a 4xxxx
register area. This holding register area can be read from an external
device, and an external device can modify the register values by writing
to them.
There are no setup parameters for mapping the data to the 4xxxx regis-
ter. The mapping is pre-defined and corresponds directly to the drive
parameter grouping which is being used by the local drive panel.
All parameters are available for both reading and writing. The parame-
ter writes are verified for correct value, and for valid register addresses.
Some parameters never allow writes (including actual values), some
parameters allow write only when the drive is stopped (including setup
variables), and some can be modified at any time (including actual ref-
erence values).
Register Mapping
The drive parameters are mapped to the 4xxxx area so that:
•
40001 – 40096 are reserved for data sets.
•
40101 – 49999 are reserved for parameters.
In this mapping, the thousands and hundreds correspond to the group
number, while the tens and ones correspond to the parameter number
within a group. Register addresses 4GGPP are shown in
Table 6-1
Parameter Mapping. In this table GG is the group number, and PP is
the parameter number within the group.