Appendix B – Technical Data
NIBA-01 Installation and Start-up Guide
B-3
NIBA-01
Enclosure: Plastic, dimensions 45 × 75 × 105 mm; degree of
protection IP 20
Mounting: Onto a standard mounting rail
Settings: Via drive interface (Control panel)
Current Consumption: 160 mA at 24 V d.c.
Communication Parameters:
Communication Parameter
Value
Device Name/Type
NIBA-01
ID Code
PCP Mode: 243 ( F3h)
IO Mode: 3 (03h)
Length Code
4 (04h)
No. of Process Data Bytes In/Out
6/6
No. of Parameter Data Bytes In/Out (PCP Mode only)
2/2
Register Length (bytes)
8
Profile No.
0
Services Supported
All mandatory services,
Get-OV, Read, Write
Maximum PDU Length
64 bytes
COMMUNICATION REFERENCE LIST ENTRIES
Max-PDU Sending-High-Prio
0
Max-PDU Sending-Low-Prio
64 bytes
Max-PDU Receiving-High-Prio
0
Max-PDU Receiving-Low-Prio
64 bytes
PMS-Services-Supported
80 30 00 / 00 00 00;
Client / Server