3BSE083678
21
Section 3 Installation
Type tests and environmental conditions
Environmental
phenomena
Basic standard Description
Test levels
ESD
EN 61000-4-2
Enclosure
Contact: ±6 kV
Air: ±8 kV
Fast transients
EN 61000-4-4
Power port
±2 kV
Signal ports
±2 kV
Surge
EN 61000-4-5
Power port
Line to earth: ±2 kV
Line to line: ±1 kV
Signal ports
Line to earth: ±2 kV
Line to line: ±1 kV
Power frequency
magnetic field
EN 61000-4-8
Enclosure
300 A/m; 0, 16.7, 50 Hz
Pulsed magnetic field EN 61000-4-9
Enclosure
300 A/m
Radiated RF
immunity
EN 61000-4-3
Enclosure
20 V/m @ (80 – 2700) MHz
10 V/m @ (2700 – 6500) MHz
1 kHz sine, 80% AM
Conducted RF
immunity
EN 61000-4-6
Power port
10 V, 80% AM, 1 kHz; (0.15 – 80) MHz
Signal ports
10 V, 80% AM, 1 kHz; (0.15 – 80) MHz
Radiated RF
emission
CISPR 16-2-3
Enclosure
Class B (30 – 6000 MHz)
ANSI C63,4
(FCC Part 15)
Class B (30 – 6500 MHz)
Conducted RF
emission
CISPR 16-2-1
Power port
Class B
Signal ports
Class B
Dielectric strength
EN 60950-1
Power interface
to all other
1.5kV AC @ 60s duration
TX signal inter-
face to all other
1.5kV AC @ 60s duration
TX shield inter-
face to all other
1.5kV AC @ 60s duration
Содержание NE802