Section 2 Interface Specifications
Power
NE802 supports redundant power connection. The positive inputs are +DC1 and
+DC2, the negative inputs for both supplies are COM. The power is drawn from the
input with the highest voltage
TX
Ethernet TX connection (RJ-45 connector), automatic MDI/MDI-X crossover.
4-pos screw terminal Description
Power
1
COM
0 V
2
+DC1
9.6–57.6 VDC
3
+DC2
9.6–57.6 VDC
4
COM
0 V
Contact
Direction
Description/Remark
1
In/Out
BI_DA+
2
In/Out
BI_DA-
3
In/Out
BI_DB+
4
In/Out
BI_DC+
5
In/Out
BI_DC-
6
In/Out
BI_DB-
7
In/Out
BI_DD+
8
In/Out
BI_DD-
Shield
In/Out
Connected to PE
1234
8
7
6
5
4
3
2
1
CAT 5 cable is recommended.
Unshielded (UTP) or shielded (STP) connector might be used.