![ABB NCAN-02 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/abb/ncan-02/ncan-02_installation-and-startup-manual_2751035.webp)
Chapter 6 – Communication
NCAN-02 Installation and Start-up Guide
6-3
The NMT commands used for controlling the node are:
Note:
If
Node ID
equals 0, all NMT slaves are addressed.
The node state indications are as follows:
Command
Name
001
Start_Remote_Node
002
Stop_Remote_Node
128
Enter_Pre-Operational_State
129
Reset_Node
130
Reset_Communication
Header
Byte
1
2
0000000000000010
NMT Command
Node ID
Indication
State
4
Prepared
5
Operational
127
Pre-Operational