![ABB MRP31.0 Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/abb/mrp31-0/mrp31-0_technical-description_2747017.webp)
- 17 -
Technical description MRP31.0
Issue: 09.2014
Technical data
Data at T
a
= 25 °C and rated values, unless otherwise indicated
General data
Supply voltage
24 V DC + 30% / - 20% (19.2 … 31.2 V DC)
Current consumtion
30 mA
Supported Communication Protocols
Modbus RTU
Physical Interface
2-wire RS485
Integrated termination resistors
no
Possible bus addresses (set via UMC100)
1 ... 125
Max. baudrate
57,6 kBit/s
Pollution degree
3
Standards / directives
Product standard
Modbus Specifi cation
RoHS Directive
2002/95/EC
Environmental data
Ambient air temperature
Operation
0 ... +60 °C
Storage
-25 ... +70 °C
Vibration (sinusoidal) acc. to IEC/EN 60068-2-6 (Fc)
4 g / 10 .... 150 Hz
Shock (half-sine) acc. to IEC/EN 60068-2-27 (Ea)
15 g / 11 ms
General Data
Degree of protection
IP20
Mounting
UMC100.3
SMK3.0
Mounting position
Any
Altitude
4000 m
Duty time
100 %
Weight
0,039 kG