Severity level
Description
Type test
Level VR3- ≤5%
Voltage Ripple of DC
IEC 60870-2-1-1995
-40°C~+75°C
Nonoperational Temperature
Range
IEEE C37.90
-30°C (Start Up)~+65°C
Operational Temperature
Range
IEEE C37.90
Table 6.2-3 Environmental standard compliance
Severity level
Description
Type test
-30°C Start Up for 16 hours
Cold Temperature
IEC 60068-2-1
+65°C Start Up for 16 hours
Dry Heat Temperature
IEC 60068-2-2
Test Db 6 25°C/+55°C
93%/95% (1 cycle=24hrs)
Humidity (Damp heat, Cyclic)
IEC 60068-2-30
95% (non-condensing) 40°C 2d
Humidity (Damp heat, Steady
state)
IEC 60068-2-3
10-200-500-200-10Hz (1g/1.5g)
X/Y/Z axes
Vibration
IEC 60870-2-2-1996
10g 11ms X/Y/X axes
Shock
IEC 60870-2-2-1996
10g, repeat 1000 times X/Y/Z
axes
Bump (Packed)
IEC 60068-2-29-1987
10g, repeat 1000 times X/Y/Z
axes
Bump (Unpacked)
IEC 60068-2-29-1987