Value
Description
System option and interface
Yes/No
This option should be selected,
if the database mirroring func-
tions are used and this system
acts as a Host. The Host is the
system that provides process
data to another system.
For example, if you use mirror-
ing between a communication
server (front-end) and a system
server, the communication
server is the host.
Database mirroring HOST
Yes/No
This option should be selected,
if the database mirroring func-
tions are used and this system
acts as an Image. The Image
is the system that receives
process data from another
system.
For example, if you use mirror-
ing between a communication
server and a system server, the
system server is the Image.
Database mirroring IMAGE
Yes/No
This option enables the OPC
DA server function. The option
should be selected, if the sys-
tem is to be connected to an
external OPC DA Client (for
example, 800xA, HIS 600)
OPC DA Server
0...3
This option is primarily intended
for HSB systems, to which an
external OPC DA client is con-
nected (for example, HIS 600).
This Application OPC server is
installed in the OPC DA Client
computer and provides an OPC
DA server interface that auto-
matically connects to the Hot
application of the HSB system.
Note: There is NO A&E server
interface in this option.
Application OPC Server
Yes/No
This option enables the OPC
A&E server function (Alarms &
Events). The option should be
selected, if the system is to be
connected to an external OPC
A&E Client (e.g. 800xA)
OPC A&E Server
30
1MRS756804
MicroSCADA Pro
SYS 600C 1.92
Product Guide