2
CONFIGURING THE TRANSMITTER…
From ‘
2.1 Getting Started
’.
Entering ‘3’ accesses ‘Login’ item from Main Menu.
‘0’ indicates security access level 0 is in operation.
Entering ‘1’ accesses Login Enable parameter.
‘?’ shows that you can change the ‘0’ level value.
Entering password ‘
engineer
’ accesses level 2 security
level. Note the use of lower case in this example. All
passwords are case sensitive.
‘2’ indicates security access level 2 is in operation.
2.6
Changing the Value of a Parameter
2.6.1
Numerical Value Parameters
✶
Note. Many parameters, e.g. the flowrate, are calculated internally, and the new value entered will therefore be ignored.
From 2.5.1 or 2.5.2, after gaining ‘user’ or ‘engineer’ access.
Entering ‘4’ accesses Flow sub-menu from Main Menu:
Item 1 (Flow Range) displayed.
‘88.50’ indicates present 100% Flow Range
or ‘Upper Range Value’ (‘URV’)
2.5.2
Gaining Access to the Engineer Level
Read 1>
Read 1>
3
Login En 1>
0
❙
1
Login En 1>
0 1
Login En 1>
0?
❙
Login En 1>
0? engineer
Login En 1>
2
❙
e
n
g
i
3
n
e
e
r
Read 1>
Read 1>
4
Flow Rng 1>
88.50
❙
4