11

A1.1

Programming The Transmitter with a Data Terminal

The nine-pin transmitter front panel connector is compatible with most serial devices, e.g. PSION Organiser, IBM PC, using
proprietary adaptors where required. This connection is for ‘local’ use only, i.e. for up to approximately 5 metres between
transmitter and data terminal.

The optional RS422/423 interface may be used for considerably greater distances (see 

Installation Manual

 for connections).

Most serial data terminals may be connected to the transmitter providing that the following three requirements are met:

1. The data rate (transmit and receive) is 4800 Baud.

2. The data format is:

3. Format for computer entry is as above plus the control codes to alter response are typically as follows:

Where

‘X OFF’ suppresses character echo and the reply consists of the value only.

‘ESC’ forces the parameter number to start from the top of the Menu Tree.

’ Separates the Parameter Number from the New Value.

N.B.

If no value is entered before pressing 

ENTER

RETURN

 etc, the current value is retained.

X

 

ON

 and/or 

ENTER

 will cancel the 

X

 

OFF

 control.

Consult the Handbook for your particular terminal device.

A1.2

Using Personal Computers with MagMaster

Many communications software packages are available and in use, and can be used to interface with the MagMaster™.

The following is a sample of typical communications programmes and setup details for interfacing with the MagMaster™.

A personal computer can be used to communicate with MagMaster to set up its operating parameters. The only requirements are:

1) The computer can be any make or type (eg. Apple, BBC, Atari, Amiga, PC etc.) but it must be equipped with a serial

communications port capable of operation at 4800 baud. (RS232C is the most common type). Most computers are fitted with
this as standard. It is not possible to give specific instructions for all types of computer, because of the large number of
computers available, but reference to the instructions of the machine to be used will provide the necessary information. A
“dumb terminal”, usually found connected to a mainframe computer, can also be used for configuring MagMaster.

2) The computer must be equipped with Terminal emulation software. In many machines (for example the BBC computer) this

is built in, in others (IBM PC and AT for example) this has to be added. The software is not special in any way and there are
many programmes on the market which provide or include this function, all of which are suitable for MagMaster use. Typical
examples for the IBM PC/AT are:

Central Point’s PC Tools

(Desktop Telecommunications)

Microsoft Windows

(Built in Terminal Emulator )

Odyssey

(Shareware programme )

Procomm Plus

(Shareware programme)

VBC.EXE

(ABB Kent-Taylor)

AQUAMAG.EXE

(VBC.EXE upgrade)

1 start bit

8 data bits, no parity

(ASCII code)

1 stop bit

X OFF

ESC

X OFF

Parameter Number

Optional New Value

APPENDIX A

Содержание MagMaster

Страница 1: ...Electromagnetic Flowmeter MagMaster Configuration Manual IM MAGMAS CM_4...

Страница 2: ...conditions result in degraded process system performance leading to personal injury or death Therefore comply fully with all Warning and Caution notices Information in this manual is intended only to...

Страница 3: ...s 1 to 3 are generally accessible the remainder are password protected Files in the drawers of the cabinet would represent the groups of parameters provided by the transmitter which if required may be...

Страница 4: ...the direction of the cable glands Special software is not required for configuring the transmitter any communication program will suffice Connect the programming terminal to the transmitter See APPEN...

Страница 5: ...TRANSMITTER 2 2 Looking at the Main Menu 2 3 Choosing a Main Menu Item Read 1 Read 1 Disp 2 Disp 2 Login 3 Login 3 Quit Q Quit Q Read 1 1 2 3 Q 1 Read 2 Disp 3 Login Part of Main Menu OR OR OR Quit FI...

Страница 6: ...r value displayed Login En Item 1 of Login menu opened and parameter value displayed Read 1 3 Login En 1 0 Read 1 Q Bye Quit Read Flow 1 32 49 5 Read Net 5 21 49 Closes any open drawers of filing cabi...

Страница 7: ...ions Set up pulse output and totaliser Set up totaliser units Set up alarm operation Set up input contact function Set up empty pipe detection Sensor calibration details etc Test operation of flowmete...

Страница 8: ...ss level 2 is in operation 2 6 Changing the Value of a Parameter 2 6 1 Numerical Value Parameters Note Many parameters e g the flowrate are calculated internally and the new value entered will therefo...

Страница 9: ...lected 1 Unit selected 0 Unit not selected Entering 1 accesses Flow Unit Ltr parameter 1 shows that you can change this logic 0 value Entering 1 selects this units parameter All other parameters in th...

Страница 10: ...es that it is possible to change the value to a 1 if required Any route through the tree structure can be similarly processed if the associated numbers and or letters for the route is known e g ESC 8...

Страница 11: ...ibed in APPENDIX A Select Engineer security level see Configuration Section Set Test Mode parameter to 1 and enter an appropriate flow rate in the Test Flow parameter Output responses may now be viewe...

Страница 12: ...e sensor Value 50 Value 1000 Check trip value A1 Measure d c voltage on DS1 DS2 w r t SIG GND AM layers removed 1 V Investigate electrode signal voltages Replace transmitter Does alarm clear Clean ele...

Страница 13: ...ample of typical communications programmes and setup details for interfacing with the MagMaster A personal computer can be used to communicate with MagMaster to set up its operating parameters The onl...

Страница 14: ...e Edit Create new entry to enter the serial settings as required above and use Modem Setup to select the COMMS Port Use F8 or select Manual to run the utility as a terminal emulator Press ALT and ESC...

Страница 15: ...em screen hold down and press I 7 Press key to select disk and then and to select C The top line should now show Comms app If so press Enter If not press the and then use the and keys to select it the...

Страница 16: ...1 HAND NONE PROTOCOL NONE ECHO HOST WIDTH NONE TIMEOUT NONE REOL CR LF REOF NONE RTRN NONE TEOL CR TEOF NONE TTRN NONE Enter the following numbers to give the operations shown in the above 13 10 CR LF...

Страница 17: ...Flow Unit Cuft Flow Unit Quiti 1 2 3 4 5 Q Read Disp Login Flow Anlg Pls Tot Alm Input Mtsnsr Snsr Test Quit 1 2 3 4 5 6 7 8 9 B C Q Anlg Fsd Anlg Zero Anlg Dir Anlg No2 Anlg mA Anlg Hart Anlg Quit 1...

Страница 18: ...VEL 1 SECURITY LEVEL 2 Tot Mult m Tot Mult c Tot Mult Tot Mult h Tot Mult k Tot Mult M Tot Mult Quit 1 2 3 4 5 6 Q 72 1 2 3 Q 8 Alm No2 Idle Alm No2 En Alm No2 Fault Alm No2 Fwd Alm No2 Rev Alm No2 Cu...

Страница 19: ...rate in chosen units Flowrate as a percentage of range Accumulated total in forward totaliser Accumulated total in reverse totaliser Net Total Forward minus Reverse Cyclic display of active alarms Tru...

Страница 20: ...Flow Time Hr Flow Time Dy Flow Time Wk Flow Time Quit 1 1 2 0 3 0 4 0 5 0 Q Flow Rspns 5 Display Setting 2 3 4 5 6 7 8 9 Seconds 2 3 4 8 15 30 60 120 Enter main full scale 100 flow range Upper Range...

Страница 21: ...ds to forward flow Analogue output responds to reverse flow Enter Q CR to return to Anlg Menu or CR to cycle around this menu Full scale flow range for second analogue range as percentage of main flow...

Страница 22: ...turn to Flow Menu or CR to cycle around this menu Select totaliser measurement units Select multiplier units required Milli 0 001 Centi 0 01 Unity 1 Hundreds 100 Thousands 1000 Millions 1000000 Enter...

Страница 23: ...Alarm occurs for forward flow Alarm occurs for Pulse Output Cutoff Alarm occurs for empty sensor Alarm occurs for Flow Alm Trip Hi Alarm occurs for Analogue Output Overange Alarm occurs for Pulse Out...

Страница 24: ...or Hi normal 0 for Lo normal Enter Q CR to return to Main Menu or CR to cycle around this menu Set up empty pipe detection Set empty pipe detector trip threshold Actual measured value related to fluid...

Страница 25: ...ly Clr indicates no alarms active Live flow velocity uncorrected for sensor calibration Enter Q CR to return to Main Menu or CR to cycle around this menu If the sensor is empty or disconnected the ala...

Страница 26: ...24 NOTES...

Страница 27: ...rumentation pH conductivity and dissolved oxygen transmitters and sensors ammonia nitrate phosphate silica sodium chloride fluoride dissolved oxygen and hydrazine analyzers Zirconia oxygen analyzers k...

Страница 28: ...County Line Road Warminster PA 18974 USA Tel 1 215 674 6000 Fax 1 215 674 7183 ABB has Sales Customer Support expertise in over 100 countries worldwide www abb com The Company s policy is one of cont...

Отзывы: