9.3 Wiring and Connection of Sensor
The sensor cable has 4 connection pairs as below
·
V
supply
(+5V) & Com
·
X – Axis & GND
·
Y – Axis & GND
·
Z – Axis & GND
Locate Connector X54 on the DAU Board and refer following illustration for identifying the MFS
Connections.
Terminal layout in DAU:
The MFS connections must be in the following order
X54 B0 Ch4 - Channel 4 – X - Axis
X54 B0 Ch5 - Channel 5 – Y - Axis
X54 B0 Ch6 - Channel 6 – Z - Axis
Note the polarity
while connecting the sensor inside DAU.
Locate connector X85 on the DAU board and connect the V
supply
, identified as +5V & Ground to the Supply
connector as indicated in Terminal Layout above.