Climatic conditions
Operating temperature
-25 to 70 °C (K70 acc. to IEC 61557-12)
Storage temperature
-40 to 85 °C (K70 acc. to IEC 61557-12)
Relative humidity
Max 93% (non-condensing) at 40°C
Pollution degree
2
Altitude
< 2000 m
Mounting requirement
Only for internal usage
User Interface
Access to device
5 pushbuttons
Display type
Graphic color display
Display dimensions
70 x 52 mm (3.5")
Communication protocol
Modbus RTU
M4M 20 Modbus, M4M 20 I/O, M4M 20 Rogowski, M4M
20-M Modbus
Communication interface
RS485 with optical isolation
Baud rate
9.6, 19.2, 38.4, 57.6, 115.2 kbps
Parity number
Odd, Even, None
Stop bit
1, 2
Address
1-247
Connector
3 pole terminal
Profibus DP-V0
M4M 20 Profibus
Protocol
Profibus with slave DP-V0 function in
compliance with IEC 61158 regulations
Communication interface
RS485 with optical isolation
Baud rate
Automatic detection [9.6k - 12 Mbps]
Address
0-126
Connector
DB 9 female connector (do not use
connectors with 90° cable outlet)
LED indicators
Green for communication status
Red for communication error
Modbus TCP/IP
M4M 20 Ethernet, M4M 20-M Ethernet
Protocol
Modbus TCP/IP
Communication interface
RJ45
BACnet
M4M 20 Bacnet
Protocol
BACnet/IP
Communication interface
RJ45
Bluetooth
Type
BLE (Bluetooth Low Energy)
Standards
Power metering and monitoring devices (PMD)
IEC 61557-12 (IEC 62053-22, IEC 62053-23)
Electrical safety
IEC 61010-1
EMC
IEC 61326-1 (IEC 61000-3-2, IEC 61000-3-3,
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-
4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-
8, IEC 61000-4-11)