CONFIGURATION PAGES
HMI MP53/MP56
1TNC928250M0201
43
4.4.2
Feeder information setting
This is the fundamental information of the feeder which include,
•
Feeder control
•
Feeder Information
Level 1
Level 2
Level 3
Value range
(PARA: Parameters)
(FCON: Feeder
control)
(ECTP: External CT Pri-
mary)
1-10000 A
(ECTS: External CT Sec-
ondary)
1A/5 A
(FEEd: Feedback)*
Current: current feed-
back,
Switch: main switch
feedback
(EPU: External PT
Used)
/
(Disable/Enable)
(EPP: External PT Pri-
mary)
600-50000
(EPS: External PT Sec-
ondary)
100-690
(InFo: Feeder Info.)
(PHAS: Number of
Phases)
1/3/3+N
(U: Voltage)
110-690
(F: Frequency)
50/60
(P: Feeder Power Rat-
ing)
0.001-4000000.000
KW
(In: Feeder Nominal
Current)
0.01-10000 A
*Feedback is part of the monitoring function of main switch device status on/off. There are
two options available, i.e. via current measurement or main switch feedback (via DI0).