background image

KLF Loss-of-Field Relay

41-748P

3

between the R and L lead. The actual per unit values
which appear on the tap plate between taps are
0,.03,.06, and.06.

The auto transformer makes it possible to expand the
basic ranges of the long and the short reach com-

pensators by a multiplier of

. Any relay ohm set-

ting can be made within 

±

 1.5 percent from 2.08

ohms to 56 ohms for the long reach and from 0 ohms
to 18 ohms for the short reach.

2.3 IMPEDANCE TRIPPING UNIT

The impedance unit is a four-pole induction-cylinder
type unit. The operating torque of the unit is propor-
tional to the product of the voltage quantities applied
to the unit and the sine of the phase angle between
the applied voltages. The direction of the torque so
produced depends on the impedance phasor seen
by the relay with respect to its characteristic circle.

Mechanically, the cylinder unit is composed of four
basic components: a die-cast aluminum frame, an
electromagnet, a moving element assembly, and a
molded bridge. The frame serves as a mounting
structure for the magnetic core. The magnetic core
which houses the lower pin bearing is secured to the
frame by a locking nut. The bearing can be replaced,
if necessary, without having to remove the magnetic
core from the frame.

The electromagnet has two sets of two series con-
nected coils mounted diametrically opposite one
another to excite each set of poles. Locating pins on
the electromagnet are used to accurately position the
lower pin bearing, which is mounted on the frame,
with respect to the upper pin bearing, which is
threaded into the bridge. The electromagnet is
secured to the frame by four mounting screws.

The moving element assembly consists of a spiral
spring, contact carrying member, and an aluminum
cylinder assembled to a molded hub which holds the
shaft. The hub to which the moving contact arm is
clamped has a wedge-and-cam construction, to pro-
vide low-bounce contact action. A casual inspection
of the assembly might lead one to think that the con-
tact arm bracket does not clamp on the hub as tightly
as it should. However, this adjustment is accurately
made at the factory and is locked in place with a lock
nut and should not be changed. Optimum contact
action is obtained when a force of 4 to 10 grams
pressure applied to the face of the moving contact
will make the arm slip from the condition of reset to
the point where the clamp projection begins to ride

up on the wedge. The free travel can vary between
15 and 20

°

.

The shaft has removable top and bottom jewel bear-
ing. The shaft rides between the bottom pin bearing
and the upper pin bearing with the cylinder rotating in
an air gap formed by the electromagnet and the mag-
netic core. The stops are an integral part of the
bridge.

The bridge is secured to the electromagnet and
frame by two (2) mounting screws. In addition to
holding the upper pin bearing, the bridge is used for
mounting the adjustable stationary contact housing.
This stationary contact has .002 to.006 inch follow
which is set at the factory by means of the adjusting
screw. After the adjustment is made the screw is
sealed in position with a material which flows around
the threads and then solidifies. The stationary con-
tact housing is held in position by a spring type
clamp. The spring adjuster is located on the under-
side of the bridge and is attached to the moving con-
tact arm by a spiral spring. The spring adjuster is also
held in place by a spring type clamp.

When the contacts close, the electrical connection is
made through the stationary contact housing clamp,
to the moving contact, through the spiral spring and
out to the spring adjuster clamp.

2.4 DIRECTIONAL UNIT

The directional unit is an induction-cylinder unit oper-
ating on the interaction between the polarizing circuit
flux and the operating circuit flux.

Mechanically, the directional unit is composed of the
same basic components as the distance unit: A die-
cast aluminum frame, an electromagnet, a moving
element assembly, and a molded bridge.

The electromagnet has two series-connected polariz-
ing coils mounted diametrically opposite one another;
two (2) series-connected operating coils mounted
diametrically opposite one another; two (2) magnetic
adjusting plugs; upper and lower adjusting plug clips,
and two (2) locating pins. The locating pins are used
to accurately position the lower pin bearing which is
mounted on the frame, with respect to the upper pin
bearing, which is threaded into the bridge. The elec-
tromagnet is secured to the frame by four mounting
screws.

The moving element assembly consists of a spiral
spring, contact carrying member, and an aluminum
cylinder assembled to a molded hub which holds the
shaft. The shaft has removable top and bottom jewel
bearings. The shaft rides between the bottom pin

S

1

M

±

--------------

Содержание KLF

Страница 1: ...e unit with adjustable resistor telephone relay and an ICS indi cating contactor switch 2 1 COMPENSATOR The compensators which are designated TA and TC are two winding air gap transformers Figure 10 page 21 The primary or current winding of the lon greach compensator TA has seven taps which termi nate at the tap block They are taps which terminate at the tap block They are marked 2 3 3 16 4 35 5 9...

Страница 2: ... Figure 1 Type KLF Relay Photo 9664A65 RV Directional Unit Reversing Links Impedance Unit Undervoltage Unit XD Resistor for X Unit X Unit ICS Front View elephone elay Rear View CB Capacitors CD Reactor T TC TA SA SC CV RB Photo 9664A66 ...

Страница 3: ...he moving contact will make the arm slip from the condition of reset to the point where the clamp projection begins to ride up on the wedge The free travel can vary between 15 and 20 The shaft has removable top and bottom jewel bear ing The shaft rides between the bottom pin bearing and the upper pin bearing with the cylinder rotating in an air gap formed by the electromagnet and the mag netic cor...

Страница 4: ...g the trip circuit Also during this operation two fingers on the arma ture deflect a spring located on the front of the switch which allows the operation indicator target to drop The target is reset from the outside of the case by a push rod located at the bottom of the cover The front spring in addition to holding the target pro vides restraint for the armature and thus controls the pickup of the...

Страница 5: ...KLF Loss of Field Relay 41 748P 5 Figure 2 Internal Schematic of Type KLF Relay in FT 41 Case Sub 10 184A958 ...

Страница 6: ...41 748P KLF Loss of Field Relay 6 Figure 3 External Schematic of Type KLF Relay Figure 4 Generalized External Schematic Sub 12 290B607 Sub 3 3491A03 ...

Страница 7: ...n Figure 12 C how VPOL is reversed by the ZC compensation In this case the ZA compensation has no effect on the balance point This explains why the reach point is fixed independently by ZC Figure 12 assumes that ZC is positive circle includes origin If the current coil link is reversed the com pensation becomes 1 5 IA ZC In Figure 12 B this change would result in VPOL being reduced rather than inc...

Страница 8: ...gs and relative advan tages of these various configurations are summa rized in Table 1 page 9 The single zone and two zone setting recommenda tions are modified when two or more machines are bussed at the machine terminals The voltage and time delay considerations are treated in detail in other sections of this leaflet The recommended set tings are outlined in Table 2 page 9 5 2 ZONE 2 SETTING CAL...

Страница 9: ...e to LOF condition 2 Can operate on partial LOF 3 Provide alarm features for manual operation 1 Same as 1 2 and 3 at left 2 Provides back up protection Table 2 Special Settings for Multi Machines Bussed at Machine Terminals Zone 1 Alone Zone 2 Alone Both Zone 1 and Zone 2 IMPEDANCE SETTING See Figure 5 See Figure 6 See Figures 5 6 VOLTAGE SETTING a Contact shorted or b Set at 87 for security 87 Zo...

Страница 10: ...A per unit X Zbase 3 ZC ZC per unit X Zbase 2R ZA X Zbase 4 where R radius of circle in per unit The tap plate settings are made according to equations 5 where T compensator tap value S autotransformer primary tap M autotransformer secondary tap value M is a per unit value determined by taking the sum of the values between the L and the R leads The sign is positive when L is above R and acts to lo...

Страница 11: ...KLF Loss of Field Relay 41 748P 11 Figure 5 Zone 1 Impedance Characteristic Figure 6 Zone 2 Impedance Characteristic Sub 3 3491A03 Sub 3 3491A03 ...

Страница 12: ...ted to the same bus loss of field of one unit may not depress the bus voltage to the point where the undervoltage unit will operate if it has the standard setting The following recommenda tions should be considered 1 For cross compound turbine generator appli cations the dropout voltage i e the voltage at which the back contact of the undervolt age unit closes of the undervoltage unit should be se...

Страница 13: ...KLF impedance circle should be small and fully offset in the nega tive reactance region The long reach should be set above synchronous reactance Xd The short reach should be set equal to one half transient reactance Xd 2 The trip circuit should be energized directly with no time delay The alarm circuit should operate a timer which may be set from 0 25 to 1 0 sec onds depending on user preference I...

Страница 14: ...s for which an M setting can be made are from 15 to 15 in steps of 03 The value of a setting is the sum of the numbers that are crossed when going from the R lead position to the L lead position The sign of the M value is determined by which lead is in the higher position on the tap plate The sign is posi tive if the L lead is higher and negative if the R lead is higher An M setting may be made in...

Страница 15: ...48P 15 Figure 7 KLF Frequency Response for 60 Hertz Impedance Unit Figure 8 Typical Machine Capacity Curves Plotted on a Per Unit kVA basis 183 500 kVA 45 H2 18 kV 0 9 pt 0 64 SRC inner cooled 3600 rpm Sub 2 3491A08 Sub 3 185A183 ...

Страница 16: ...minal voltage at 80 volts increase current until contacts just close This current should be within 3 of 2 25 amp 2 32 2 18 amp This value corre sponds to 1 5ZA setting since the voltage is applied to terminals 4 and 5 is equivalent to 1 5 VIN voltage or 4 Adjust phase shifter for 90 current leading the voltage 5 With the terminal voltage at 80 volts increase current until contacts just close This ...

Страница 17: ...ad should be connected to the 0 insert R lead should be connected to the upper 06 insert 03 06 06 15 between L and R For the most accurate calibration preheat relay for at least an hour by energizing terminals 5 6 7 with 120 volts 3 phase The links in the middle tap block should be set for the TC direction vertical 1 Contact Gap Adjustment The spring type pressure clamp holding the sta tionary con...

Страница 18: ... should not be loosened prior to rotating the spring adjuster The adjust ment of the spring is accomplished by rotating the spring adjuster which is located on the under side of the bridge The spring adjuster has a notched periphery so that a tool may be used to rotate it 3 Plug adjustment for reversing of spurious torques a Set TC 0 0 Connect a heavy current lead from TA center link to terminal 8...

Страница 19: ... the telephone relay coil is shorted This may be done by manually closing the impedance unit Z and direc tional unit D contacts H Compensator Check Accuracy of the mutual impedance T of the compen sators is set within very close tolerances at factory and should not change under normal conditions The mutual impedance of the compensators can be checked with accurate instruments by the procedure outl...

Страница 20: ...41 748P KLF Loss of Field Relay 20 Figure 9 Typical Machine Capability Curves and Sample KLF Setting Sub 2 185A184 ...

Страница 21: ...KLF Loss of Field Relay 41 748P 21 Figure 11 R X Diagram Characteristics with Various ZC Compensator Settings Sub 2 185A182 Figure 10 Compensator Construction Sub 1 185A181 ...

Страница 22: ...41 748P KLF Loss of Field Relay 22 Figure 12 Effect of Compensator Voltages ZC is positive Sub 3 185A331 ...

Страница 23: ...KLF Loss of Field Relay 41 748P 23 Figure 13 Diagram of Test Connections for KLF Relay Sub 5 290B580 ...

Страница 24: ... Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 41 748P KLF Loss of Field Relay ABB Automation Inc Figure 14 Outline and Drilling Plan for the Type KLF Relay in the FT 41 Case Sub 18 57D7904 ...

Отзывы: