background image

KLF Loss-of-Field Relay

41-748P

13

C. The desired undervoltage unit setting is com-

puted by:

Setting = V

AT

 = 1.5 V

AN

where V

AN

 is phase-to-neutral voltage.

Note:

An electrical check of this particular set-

ting is outlined in this instruction leaflet,
under the heading “Acceptance Check”
.

5.5 TIME DELAY CONSIDERATIONS

It may be conservatively stated that the rotor struc-
ture and stator heating, as a result of a shorted field
can be tolerated for 10 seconds on a conductor-
cooled machine and 25 seconds for a conventional
machine. This time may be as low as 5 seconds for
an open field (as opposed to a field closed through a
field discharge resistor or an exciter armature) and
as high as one minute where the concern is protec-
tion of an adjacent tandem compound unit against
partial loss-of-excitation in the faulted machine.

In view of the above considerations, it is often desir-
able to use an external timer in conjunction with the
KLF Relay. The following examples are applications
where an external timer would be desirable.

1.

Cross-compound units, with undervoltage
unit setting of 90 volts, should use an exter-
nal timer to assure tripping before thermal
damage can result. The timer is energized at
the alarm output and should be set for 10
seconds for a cross-compound conductor
cooled machine. For a conventionally cooled
cross-compound machine, the external timer
should be set for 25 seconds.

As an alternative to this, the KLF with
shorted undervoltage contacts may be
applied and the alarm feature not used. With
this arrangement, tripping takes place after
the 200 ms time delay provided by the X unit
in the KLF relay.

2.

Machines connected to a common high volt-
age bus may be protected against loss of
voltage due to loss-of excitation in a adjacent
machine by using a one minute timer driven
by the alarm output of the loss-of-field relay.

3.

In some critical applications 2-zone loss-of-
field protection may be desirable. In this
case, the Zone-1 KLF impedance circle
should be small and fully offset in the nega-
tive reactance region. The long-reach should
be set above synchronous reactance, Xd.
The short-reach should be set equal to one-

half transient reactance, X

d

/2. The trip circuit

should be energized directly, with no time
delay. The alarm circuit should operate a
timer which may be set from 0.25 to 1.0 sec-
onds, depending on user preference. If the
condition persists, this timer permits tripping.

The second-zone KLF may be set with a
larger impedance characteristic and will
detect partial loss-of-field conditions. A typi-
cal setting would be to just allow the machine
to operate at maximum hydrogen pressure
and 0.95 per unit voltage. If a low voltage
condition occurs, it is recommended that trip-
ping be accomplished through a timer set for
0.8 seconds. Added to the X unit dropout
time of 0.2 seconds, this gives an overall
time of 1.0 second. If the voltage is main-
tained, then the alarm circuit should start a
“last-ditch” timer. This timer may be set any-
where from 10 seconds to one minute
depending on machine type and user prefer-
ence.

5.6 PERFORMANCE DURING REDUCED 

FREQUENCY

During major system break-ups, it is possible that the
generators may be called upon to operate at reduced
frequency for long periods of time. During this condi-
tion the loss-of-field relay should be secure and not
over-trip for load conditions. The KLF relay has a
favorable characteristic during this condition, since
this tripping characteristic becomes more secure dur-
ing reduced frequencies, as shown Figure 7, page
15.

6.0

SETTING THE RELAY

The type KLF relay requires a setting for each of the
two compensators T

A

 and T

C

, for each of the two

autotransformers, primaries S

A

 and S

C

, and for the

undervoltage unit.

6.1 COMPENSATOR (T

A

 AND T

C

)

Each set of compensator taps terminates in inserts
which are grouped on a socket and form approxi-
mately three quarters of a circle around a center
insert which is the common connection for all the
taps. Electrical connections between common insert
and tap inserts are made with a link that is held in
place with two connector screws, one in the common
and one in the tap.

Содержание KLF

Страница 1: ...e unit with adjustable resistor telephone relay and an ICS indi cating contactor switch 2 1 COMPENSATOR The compensators which are designated TA and TC are two winding air gap transformers Figure 10 page 21 The primary or current winding of the lon greach compensator TA has seven taps which termi nate at the tap block They are taps which terminate at the tap block They are marked 2 3 3 16 4 35 5 9...

Страница 2: ... Figure 1 Type KLF Relay Photo 9664A65 RV Directional Unit Reversing Links Impedance Unit Undervoltage Unit XD Resistor for X Unit X Unit ICS Front View elephone elay Rear View CB Capacitors CD Reactor T TC TA SA SC CV RB Photo 9664A66 ...

Страница 3: ...he moving contact will make the arm slip from the condition of reset to the point where the clamp projection begins to ride up on the wedge The free travel can vary between 15 and 20 The shaft has removable top and bottom jewel bear ing The shaft rides between the bottom pin bearing and the upper pin bearing with the cylinder rotating in an air gap formed by the electromagnet and the mag netic cor...

Страница 4: ...g the trip circuit Also during this operation two fingers on the arma ture deflect a spring located on the front of the switch which allows the operation indicator target to drop The target is reset from the outside of the case by a push rod located at the bottom of the cover The front spring in addition to holding the target pro vides restraint for the armature and thus controls the pickup of the...

Страница 5: ...KLF Loss of Field Relay 41 748P 5 Figure 2 Internal Schematic of Type KLF Relay in FT 41 Case Sub 10 184A958 ...

Страница 6: ...41 748P KLF Loss of Field Relay 6 Figure 3 External Schematic of Type KLF Relay Figure 4 Generalized External Schematic Sub 12 290B607 Sub 3 3491A03 ...

Страница 7: ...n Figure 12 C how VPOL is reversed by the ZC compensation In this case the ZA compensation has no effect on the balance point This explains why the reach point is fixed independently by ZC Figure 12 assumes that ZC is positive circle includes origin If the current coil link is reversed the com pensation becomes 1 5 IA ZC In Figure 12 B this change would result in VPOL being reduced rather than inc...

Страница 8: ...gs and relative advan tages of these various configurations are summa rized in Table 1 page 9 The single zone and two zone setting recommenda tions are modified when two or more machines are bussed at the machine terminals The voltage and time delay considerations are treated in detail in other sections of this leaflet The recommended set tings are outlined in Table 2 page 9 5 2 ZONE 2 SETTING CAL...

Страница 9: ...e to LOF condition 2 Can operate on partial LOF 3 Provide alarm features for manual operation 1 Same as 1 2 and 3 at left 2 Provides back up protection Table 2 Special Settings for Multi Machines Bussed at Machine Terminals Zone 1 Alone Zone 2 Alone Both Zone 1 and Zone 2 IMPEDANCE SETTING See Figure 5 See Figure 6 See Figures 5 6 VOLTAGE SETTING a Contact shorted or b Set at 87 for security 87 Zo...

Страница 10: ...A per unit X Zbase 3 ZC ZC per unit X Zbase 2R ZA X Zbase 4 where R radius of circle in per unit The tap plate settings are made according to equations 5 where T compensator tap value S autotransformer primary tap M autotransformer secondary tap value M is a per unit value determined by taking the sum of the values between the L and the R leads The sign is positive when L is above R and acts to lo...

Страница 11: ...KLF Loss of Field Relay 41 748P 11 Figure 5 Zone 1 Impedance Characteristic Figure 6 Zone 2 Impedance Characteristic Sub 3 3491A03 Sub 3 3491A03 ...

Страница 12: ...ted to the same bus loss of field of one unit may not depress the bus voltage to the point where the undervoltage unit will operate if it has the standard setting The following recommenda tions should be considered 1 For cross compound turbine generator appli cations the dropout voltage i e the voltage at which the back contact of the undervolt age unit closes of the undervoltage unit should be se...

Страница 13: ...KLF impedance circle should be small and fully offset in the nega tive reactance region The long reach should be set above synchronous reactance Xd The short reach should be set equal to one half transient reactance Xd 2 The trip circuit should be energized directly with no time delay The alarm circuit should operate a timer which may be set from 0 25 to 1 0 sec onds depending on user preference I...

Страница 14: ...s for which an M setting can be made are from 15 to 15 in steps of 03 The value of a setting is the sum of the numbers that are crossed when going from the R lead position to the L lead position The sign of the M value is determined by which lead is in the higher position on the tap plate The sign is posi tive if the L lead is higher and negative if the R lead is higher An M setting may be made in...

Страница 15: ...48P 15 Figure 7 KLF Frequency Response for 60 Hertz Impedance Unit Figure 8 Typical Machine Capacity Curves Plotted on a Per Unit kVA basis 183 500 kVA 45 H2 18 kV 0 9 pt 0 64 SRC inner cooled 3600 rpm Sub 2 3491A08 Sub 3 185A183 ...

Страница 16: ...minal voltage at 80 volts increase current until contacts just close This current should be within 3 of 2 25 amp 2 32 2 18 amp This value corre sponds to 1 5ZA setting since the voltage is applied to terminals 4 and 5 is equivalent to 1 5 VIN voltage or 4 Adjust phase shifter for 90 current leading the voltage 5 With the terminal voltage at 80 volts increase current until contacts just close This ...

Страница 17: ...ad should be connected to the 0 insert R lead should be connected to the upper 06 insert 03 06 06 15 between L and R For the most accurate calibration preheat relay for at least an hour by energizing terminals 5 6 7 with 120 volts 3 phase The links in the middle tap block should be set for the TC direction vertical 1 Contact Gap Adjustment The spring type pressure clamp holding the sta tionary con...

Страница 18: ... should not be loosened prior to rotating the spring adjuster The adjust ment of the spring is accomplished by rotating the spring adjuster which is located on the under side of the bridge The spring adjuster has a notched periphery so that a tool may be used to rotate it 3 Plug adjustment for reversing of spurious torques a Set TC 0 0 Connect a heavy current lead from TA center link to terminal 8...

Страница 19: ... the telephone relay coil is shorted This may be done by manually closing the impedance unit Z and direc tional unit D contacts H Compensator Check Accuracy of the mutual impedance T of the compen sators is set within very close tolerances at factory and should not change under normal conditions The mutual impedance of the compensators can be checked with accurate instruments by the procedure outl...

Страница 20: ...41 748P KLF Loss of Field Relay 20 Figure 9 Typical Machine Capability Curves and Sample KLF Setting Sub 2 185A184 ...

Страница 21: ...KLF Loss of Field Relay 41 748P 21 Figure 11 R X Diagram Characteristics with Various ZC Compensator Settings Sub 2 185A182 Figure 10 Compensator Construction Sub 1 185A181 ...

Страница 22: ...41 748P KLF Loss of Field Relay 22 Figure 12 Effect of Compensator Voltages ZC is positive Sub 3 185A331 ...

Страница 23: ...KLF Loss of Field Relay 41 748P 23 Figure 13 Diagram of Test Connections for KLF Relay Sub 5 290B580 ...

Страница 24: ... Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 41 748P KLF Loss of Field Relay ABB Automation Inc Figure 14 Outline and Drilling Plan for the Type KLF Relay in the FT 41 Case Sub 18 57D7904 ...

Отзывы: