IB 6.2.11.1-1C
Page 12
ABB
K-Line Plus Secondary Disconnect Assignments
Pin Description
Pin Description
A1
Charge Motor +
B1
Undervoltage Trip Device +
A2
Shunt Trip -
B2
Undervoltage Trip Device -
A3
Close Coil +
B3
(MPSC-2000 4WG or DESP)
6
A4
Shunt Trip +
B4
(MPSC-2000 4WG or DESP)
6
A5
Close Coil -
B5
(MPSC-2000 4WG or DESP)
6
A6
MPSC-2000 VIM
B6
(MPSC-2000 4WG or DESP)
6
A7
Charge Motor -
B7
Aux. Sw. "a" +
A8
Local Elec. Close +
B8
Aux. Sw. "a" -
A9
Local Elec. Trip +
B9
Aux. Sw. "b" +
A10
Alarm Switch
4
B10 Aux. Sw. "b" -
A11
Alarm Switch
4
B11 Aux. Sw. "a" +
A12
Alarm Switch
4
B12 Aux. Sw. "a" -
A13
Alarm Switch
4
B13 Aux. Sw. "b" +
A14
Aux. Sw. "a" +
B14 Aux. Sw. "b" -
A15
Aux. Sw. "a" -
B15 Aux. Sw. "a" +
A16
Aux. Sw. "a" +
B16 Aux. Sw. "a" -
A17
Aux. Sw. "a" -
B17 Aux. Sw. "b" +
A18
Aux. Sw. "b" +
B18 Aux. Sw. "b" -
A19
Aux. Sw. "b" -
B19 Aux. Sw. "a" +
A20
Aux. Sw. "a" +
B20 Aux. Sw. "a" -
A21
Aux. Sw. "a" -
B21 Aux. Sw. "b" +
A22
Aux. Sw. "b" +
B22 Aux. Sw. "b" -
A23
Aux. Sw. "b" -
B23 (Spare)
5
A24
(Spare)
5
B24 (Spare)
5
A25
(Not Used)
B25 (Not Used)
pin-out assignments.
(6) The assignments for pins B3 - B6 will differ depending on whether the DESP option has been supplied. See
the MPSC-2000 schematic supplied with the breaker.
Notes:
(1) These assignments are
provided for reference only,
and may be changed due to
special requirements. Some
pins or plugs may not be
present on all breaker
configurations. See the
breaker schematic wiring
diagram(s) for details.
(2) Note the polarity of control
devices: “+” is the send and
“-” is the return.
(3) The two terminals of each
Auxiliary Switch contact are
connected to adjacent
Secondary Disconnect pins.
For example, pins A14 and
A15 are connected to a
single “a” contact. Also, the
polarity signs are provided
on these pins for consistency
only; the Auxiliary Switch
contacts are not polarity
sensitive.
(4) The Alarm Switches can be
wired in two different ways.
See the schematic supplied
with the breaker for details
on the pin-outs.
(5)
The pins marked “(Spare)”
may be used in some
b r e a k e r s f o r s p e c i a l
c u s t o m e r w i r i n g
requirements. Refer to the
schematic wiring diagram
supplied with the breaker for
Содержание K-Line Plus KP-8
Страница 23: ...IB 6 2 11 1 1C Page 23 ABB NOTES ...
Страница 24: ...IB 6 2 11 1 1C Page 24 ABB NOTES ...
Страница 25: ...IB 6 2 11 1 1C Page 25 ABB NOTES ...