Page 5
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Step 10
-
Initial Start Up
Verify that all AC, DC and Alarm connections are complete and secure. Turn on DC input breakers. If there are no
alarms, make required adjustments to the default settings on the controller for this installation.
Step 11
-
Configure Controller per Galaxy Pulsar Edge Controller Quick Start Guide
Verify and edit controller basic configuration parameters per site engineering instructions.
Information: Controller Define Alarm Inputs and Outputs
Converter Alarm Outputs:
Select the Settings tab > Converters to set alarm thresholds, severity and relays on J1 connector.
Select the drop down arrow next to the LED field and select ALM to activate the ALM LED for that alarm condition.
Factory defaults are shown in the web page to the right.
Auxiliary Alarm Inputs:
Select the Settings tab > Auxiliary Inputs to define up to four external alarms through connector J2.
Converter Alarm Outputs: Settings tab > Converters
Auxiliary Alarm Inputs: Settings tab > Auxiliary Inputs
Information: Controller Default Voltage Settings and Ranges
Default
24V
48V
48V
24V
Converter Internal Selective High Output Voltage Shutdown
25.0 to 30.0V
50.0 to 60.0V
High Output Voltage Major Alarm
25.0 to 30.0V
50.0 to 60.0V
High Output Voltage Minor Alarm
24.0 to 30.0V
48.0 to 60.0V
Output Voltage Set
-
Point
23.0 to 27.2V
46.0 to 54.5V
Low Voltage Alarm
20.0 to 27.0V
40.0 to 54.0V