QUICK START GUIDE
Step 2
-
Plan DC Feeds
The system has three input feeds, each feeding three converter slots, and a
-
48V bulk output. Recommended
breakers and cable sizes are in the tables below.
Note: Some installations do not require protectors on the inputs.
Note: All returns should be grounded at the power system feeding the converter shelf.
NE030DC48A
Per
Amps
Input Cable Size
(minimum)
Breaker
Amps
Output Cable Size
(minimum)
80A
100A
30A
160A
(1) 2/0
200A
60A
240A
(2) 2/0
300A
90A