41-133S
15
Directional Overcurrent Ground Relays
Types IRP, IRC and IRD
ENERGY REQUIREMENTS
TIME OVERCURRENT UNITS:
IRD-5, IRC-5, IRP-5
IRD-6, IRC-6, IRP-6
VOLT AMPERES
‡
Ampere
Tap Value
TAP
Continuous
Rating
(Amperes)
One Second
Rating
†
(Amperes)
Power
Angle
φ
At
Current
At
Tap Value
Current
At
Tap Value
Current
At
Tap Value
Current
0.5
0.6
0.8
1.0
1.5
2.0
2.5
2
2.5
3
3.5
4
5
6
4
5
6
7
8
10
12
2.7
3.1
3.7
4.1
5.7
6.8
7.7
8
8.8
9.7
10.4
11.2
12.5
13.7
16
18.8
19.3
20.8
22.5
25
28
88
88
88
88
88
88
88
230
230
230
230
230
230
230
460
460
460
460
460
460
460
69
68
67
66
62
60
58
67
66
64
63
62
59
57
65
63
61
59
56
53
47
3.92
3.96
3.96
4.07
4.19
4.30
4.37
3.88
3.90
3.93
4.09
4.12
4.20
4.38
4.00
4.15
4.32
4.35
4.40
4.60
4.92
20.6
20.7
21.0
21.4
23.2
24.9
26.2
21.0
21.6
22.1
23.1
23.5
24.8
26.5
22.4
23.7
25.3
26.4
27.8
30.1
35.6
103
106
114
122
147
168
180
110
118
126
136
144
162
183
126
143
162
183
204
247
288
270
288
325
360
462
548
630
308
342
381
417
448
540
624
376
450
531
611
699
880
1056
0.5/2.5
2/6
4/12
Range
Tap Value
Thermal capacities for short times other than one second may be calculated on the basis of time being inversely
proportional to the square of the current.
Degrees current lags voltage at tap value current.
†
φ
Factor
3 Times
10 Times
20 Times
Voltages taken with high impedance type voltmeter
‡