IM300 Intelligent Power Monitoring Instrument
68
40123
RO
Active power of phase B
(
Wb
)
1
40124
RO
Active power of phase C
(
Wc
)
1
40125
RO
Reactive power of phase A
(
Qa
)
1
40126
RO
Reactive power of phase B
(
Qb
)
1
40127
RO
Reactive power of phase C
(
Qc
)
1
40128
RO
Apparent power of Phase A
(
Sa
)
1
40129
RO
Apparent power of phase B
(
Sb
)
1
40130
RO
Apparent power of phase C
(
Sc
)
1
Note 1:
In the 3-phase 3-wire system, the data in 40104
~
40107 and
40119
~
40130 are invalid and value is 0.
Note 2:
The correspondence between the above data (Ai) and the actual
value is:
Voltage: U = (Ai / 10) × (PT1 / PT2), Ai is an unsigned integer, unitV.
Current: I = (Ai / 1000) × (CT1 / CT2), Ai is an unsigned integer,
unit:A.
Zero-sequence current: In = (Ai / 1000) × (CT01 / CT02), Ai is an
unsigned integer, unit:A.
Active power: P = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed integers,
unit:W.
Reactive power: Q = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed
integers, unit:var.
Apparent power: S = Ai × (PT1 / PT2) × (CT1 / CT2), Ai is an
unsigned integer, unit:VA.
Power factor: PF = Ai / 1000, Ai denote signed integers, no unit.
Frequency: F = Ai / 100, Ai as an unsigned integer, unit:Hz.
energy address table, supports read function of codes 03, 04 and set function
of code 10.Only support writes continuously
Address
Type
Data Definition
Regist
er
40200
RW
The absolute value of total active energy
2