background image

always include the following items of information from the 
transformer’s nameplate: Serial number, style number, KVA 
rating, high voltage and low voltage ratings. 

Additionally, all applicable safety procedures such as OSHA 
requirements, regional and local safety requirements, safe 
working  practices  and  good  judgement  must  be  used  by 
such personnel. 

 

3.0 RECEIVING 

 
WARNING: 

DO  NOT  LIFT  THE  TRANSFORMER 

BY USING CRANES OR JACKS ON ANY PART OF 
THE TRANSFORMER  OTHER THAN THE  LIFTING 
HOOKS OR JACKING PADS PROVIDED FOR THIS 
PURPOSE. IMPROPER LIFTING OR JACKING CAN 
CAUSE  SEVERE  INJURY  AND/OR  PROPERTY 
DAMAGE. 

 
The Unit Substation Transformer is normally shipped as a 
complete sub-assembly and ready to install in the field with 
mating  high  voltage  switchgear  section  and  low  voltage 
section.  Each  transformer  should  be  carefully  inspected 
upon receipt and the transportation company notified of any 
damage that has been incurred. The shipping list should be 
checked for possible shortages. 

Unit  Substation Transformers  are  normally  shipped  on  a 
pallet. Palletized transformers may be moved readily by a 
lift truck, crane, or cart. The lifting hooks supplied on the 
sides of the transformer enable it to be lifted by crane. 

Be sure the device chosen has the capacity to lift, or move, 
the complete unit. (Weight is shown on the nameplate.) 

Lift the transformer utilizing all the hooks and use proper 
spreaders to obtain a vertical lift.

Air Terminal Chambers (ATC’s) with hinged access panels 
are  furnished  with  either  “hex-head”  or  when  specified 
“penta-head”  locking  bolt  that  must  be  loosened  to  open 
the compartment. This bolt can be turned with a standard 
socket (wrench), as used widely in the utility industry. 

4.0 EXTERNAL INSPECTION

 
WARNING: 

THE  OIL  MUST  BE  AT THE  PROPER 

LEVEL  (25°  C  LEVEL)  BEFORE  VOLTAGE  IS 
APPLIED  TO  THE  TRANSFORMER.  FAILURE 
TO  MAINTAIN  THE  PROPER  OIL  LEVEL  CAN 
CAUSE  SEVERE  PERSONAL  INJURY,  DEATH  OR 
SUBSTANTIAL PROPERTY DAMAGE. 

 
The oil level should be checked by inspecting the liquid level 
gauge. Any unit which does not have the proper oil level 
should be checked for leaks and refilled before placing in 
service. Refilling with oil is an unusual field condition and 
requires extreme care. The first priority is to determine the 
reason for the low oil level and may require leak repair or 
replacement of defective gaskets or seals. 

If  the  oil  level  is  slightly  below  normal  but  still  above  the 
internal  transformer  windings,  oil  can  be  added  in  the 
field  by  using  the  fill  couplings.  Refer  to  the  nameplate 
to indicate the type of oil that is used and only fill with oil 
that  is  approved. Take  caution  to  ensure  that  the  correct 
fluid  is  used  and  ensure  that  other  contaminates  are  not 
introduced.  Use  only  quality  oil  per  ASTM  D3487  when 
adding  oil  to  the  transformer.  The  transformer  was  filled 
or  processed  at  the  factory  with  non-PCB  dielectric  fluid 
in  accordance  with  Federal  Polychlorinated  Bi-phenyl 
(PCB) Regulations 40 CFR 761, et seq. The non-PCB fluid 
contained  less  than  1ppm  PCB  at  time  of  processing  or 
filling. The owner should take the necessary precautions so 
that PCB contamination is not introduced during field filling 
or maintenance of the transformer (refer to Fig. 2). 

If the oil level is below normal and the transformer 
windings are exposed to air, then field addition of 
oil is not possible as trapped air in the windings can 
lead to dielectric failure. In this case, the substation 
transformer must be returned to a service facility for 
vacuum oil filling

.  

 

Page 2

Содержание ILUJ000004-BLE

Страница 1: ... TO INSTALL MAINTAIN OPERATE OR SERVICE THE TRANSFORMER FAILURE TO FOLLOW INSTRUCTIONS CAN CAUSE SEVERE INJURY DEATH OR PROPERTY DAMAGE Keep this Instruction Book available to those responsible for the installation maintenance operation and service of the transformer Safety as defined in this Instruction Book involves two conditions Personal injury 1 Product or property damage 2 SEE IMPORTANT DISC...

Страница 2: ...et wrench as used widely in the utility industry 4 0 EXTERNAL INSPECTION WARNING THE OIL MUST BE AT THE PROPER LEVEL 25 C LEVEL BEFORE VOLTAGE IS APPLIED TO THE TRANSFORMER FAILURE TO MAINTAIN THE PROPER OIL LEVEL CAN CAUSE SEVERE PERSONAL INJURY DEATH OR SUBSTANTIAL PROPERTY DAMAGE The oil level should be checked by inspecting the liquid level gauge Any unit which does not have the proper oil lev...

Страница 3: ...egrees as a greater tilt will cause deviations in liquid level near live parts pressure relief devices or other accessories specifically located at or near the 25 degree C liquid level CAUTION DEVIATIONS FROM SPECIFIED OIL LEVEL CAN INCREASE THE POSSIBILITY OF A DISRUPTIVE FAILURE Unit substation transformers must be adequately anchored and secured to the pad When seismic conditions are specified ...

Страница 4: ...ergized transformer make sure that any protective or insulating barriers are in place the air terminal chamber is completely closed and all locking provisions are properly installed The following procedure should be used to assure air terminal chamber security A Close the left door and secure it in place with the captive bolts supplied pentahead or hexhead B Close the right door and secure it in p...

Страница 5: ...cated on the front panel of the transformer refer to Fig 11 A De energize the transformer B Back out the locking screw until it is clear of the locking hole C Turn the handle to the desired tap position D Tighten the locking screw to minimize the possibility of unintentional movement Some large size units are furnished with a power transformer tap changer drive which requires pulling of a locking ...

Страница 6: ...e the transformer other than those shown on the nameplate 9 10 Control Cabinet WARNING THE CONTROL CABINET CONTAINS CONTROL VOLTAGE AND ELECTRICAL POWER FOR COOLING FAN OPERATION ENSURE THAT CABINET IS ADEQUATELY GROUNDED AND ALWAYS REMOVE THE CONTROL CABINET POWER SUPPLY PRIOR TO PERFORMING WORK INSIDE THE CONTROL CABINET EQUIPMENT OR CONNECTED ACCESSORIES FAILURE TO DO SO COULD RESULT IN SEVERE ...

Страница 7: ...e overload Planned overloading should be in accordance with the ANSI Loading Guide C57 91 When adding oil to the transformer the owner should take the necessary precautions so that PCB contamination is not introduced WARNING OIL SAMPLES SHOULD BE TAKEN FROM THE TRANSFORMER ONLY AFTER DE ENERGIZING AND MANUALLY VENTING THE TRANSFORMER FAILURE TO DO SO CAN CAUSE SEVERE INJURY DEATH OR PROPERTY DAMAG...

Страница 8: ...formers THIS INFORMATION SHOULD NOT BE CONSIDERED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES NO WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSEORMERCHANTABILITY ORWARRANTIESARISINGFROMCOURSEOFDEALINGORUSAGEOFTRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED HEREIN In no event will ABB be responsible to...

Отзывы: